Generac RD030 troubleshooting: 27 fault codes and symptom-cause-remedy entries from the manufacturer's own service documentation.

Generac RD030 — full specs, parts & maintenance.

All Generac fault codes →

Troubleshooting

27

Symptoms & remedies

SymptomCauseRemedy
Unit consumes large amounts of oil. Engine over filled with oil.Adjust oil to correct level.
Unit will not start in AUTO with utility loss. NOT ACTIVATEDRefer to activation section in Owner’s Manual.
Unit running in AUTO but no power in house. NONECheck MLCB. Contact servicing dealer if MLCB is in the ON position.
Unit will not start in AUTO with utility loss. HIGH TEMPERATURECheck ventilation around the intake, exhaust and rear of generator. Contact serving dealer if no obstruction is found.
Unit shuts down during operation. OVERLOADClear alarm and remove household loads from the generator. Put back in AUTO and restart.
Unit was running and shuts down, attempts to restart. RPM SENSE LOSSClear alarm and remove household loads from the generator. Put back in AUTO and restart. If problem returns, contact servicing dealer to investigate possible fuel issue.
Unit will not start in AUTO with utility loss. LOW OIL PRESSURECheck oil level. Add oil per Owner’s Manual. Contact servicing dealer if oil level is correct.
Unit will not start in AUTO with utility loss. RPM SENSE LOSSClear alarm. From the MAIN menu on the control panel, navigate to the BATTERY MENU. Contact servicing dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
Unit will not start in AUTO with utility loss. OVERCRANKClear alarm. Attempt to start the unit in MANUAL. If it does not start or starts and runs rough, contact servicing dealer.
Unit will not start in AUTO with utility loss. FUSE PROBLEMCheck ATO 7.5 amp fuse. Replace with same type fuse if bad. Contact servicing dealer if fuse is good.
Unit will not start in AUTO with utility loss. OVERSPEEDContact servicing dealer.
Unit will not start in AUTO with utility loss. UNDERVOLTAGEContact servicing dealer.
Unit will not start in AUTO with utility loss. UNDERSPEEDContact servicing dealer.
Unit will not start in AUTO with utility loss. MISWIREContact servicing dealer.
Unit will not start in AUTO with utility loss. OVERVOLTAGEContact servicing dealer.
Warning active. LOW BATTERYClear alarm. From the MAIN menu on the control panel, navigate to the BATTERY MENU. Contact servicing dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
Warning active. BATTERY PROBLEMContact servicing dealer.
Warning active. CHARGER WARNINGContact servicing dealer.
Warning active. SERVICE SCHEDULE APerform SERVICE SCHEDULE A maintenance; press ENTER to clear.
Warning active. SERVICE SCHEDULE BPerform SERVICE SCHEDULE B maintenance; press ENTER to clear.
Warning active. SERVICE SCHEDULE CPerform SERVICE SCHEDULE C maintenance; press ENTER to clear.
The engine will not crank.Fuse blown.Replace 7.5 amp fuse in generator control panel. Correct short circuit condition if fuse blows again.
The engine cranks but will not start.Out of fuel.Replenish fuel. Turn on fuel valve.
The engine starts hard and runs rough.Air cleaner plugged or damaged.Check/replace air cleaner.
The generator is set to OFF, but the engine continues to run.Defective keypad.*
There is no AC output from the generator.Main line circuit breaker is in the OFF (OPEN) position.Reset circuit breaker to ON (CLOSED) position.
There is no transfer to standby after utility source failure.Defective transfer switch coil.*

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Generac RD030: The engine will not crank — what causes it?

Documented causes: Fuse blown.. See the table for the matching fixes.

Generac RD030: The engine cranks but will not start — what causes it?

Documented causes: Out of fuel.. See the table for the matching fixes.

Generac RD030: The engine starts hard and runs rough — what causes it?

Documented causes: Air cleaner plugged or damaged.. See the table for the matching fixes.