Home› Troubleshooting›Generac MMG35DF4

Generac MMG35DF4 Troubleshooting

Generac MMG35DF4 troubleshooting: 58 fault codes and 46 symptom-cause-remedy entries from the manufacturer's own service documentation.

Generac MMG35DF4 — full specs, parts & maintenance.

All Generac fault codes →

Troubleshooting

104

Fault codes

CodeMeaningCauseRemedy
HIGH TEMPERATUREUnit shuts down during operation.Check ventilation around the intake, exhaust and rear of generator. Contact Independent Authorized Servicing Dealer if no obstruction is found.
OVERLOAD REMOVE LOADUnit shuts down during operation.Clear alarm and remove household loads from the generator. Put back in AUTO and restart.
RPM SENSE LOSSUnit was running and shuts down, attempts to restart.Clear alarm and remove household loads from the generator. Put back in AUTO and restart. If problem returns, contact Independent Authorized Servicing Dealer to investigate possible fuel issue.
NOT ACTIVATEDUnit will not start in AUTO with 2-wire start signal.Refer to Activation.
LOW OIL PRESSUREUnit will not start in AUTO with 2-wire start signal.Check oil level. Add oil per Owner's Manual. Contact Independent Authorized Servicing Dealer if oil level is correct.
RPM SENSE LOSSUnit will not start in AUTO with 2-wire start signal.Clear alarm. Navigate to the BATTERY MENU on the control pad LCD. Contact Independent Authorized Servicing Dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
OVERCRANKUnit will not start in AUTO with 2-wire start signal.Check fuel line shutoff valve is in the ON position. Clear alarm. Attempt to start the unit in MANUAL. If it does not start or starts and runs rough, contact Independent Authorized Servicing Dealer.
LOW VOLTS REMOVE LOADUnit will not start in AUTO with 2-wire start signal.Clear alarm and remove household loads from the generator. Set back to AUTO and restart.
FUSE PROBLEMUnit will not start in AUTO with 2-wire start signal.Check ATO 7.5 Amp fuse. Replace with same type fuse if bad. Contact Independent Authorized Servicing Dealer if fuse is good.
OVERSPEEDUnit will not start in AUTO with 2-wire start signal.Contact Independent Authorized Servicing Dealer.
UNDER VOLTAGEUnit will not start in AUTO with 2-wire start signal.Contact Independent Authorized Servicing Dealer.
UNDERSPEEDUnit will not start in AUTO with 2-wire start signal.Contact Independent Authorized Servicing Dealer.
STEPPER OVERCURRENTUnit will not start in AUTO with 2-wire start signal.Contact Independent Authorized Servicing Dealer.
MISWIREUnit will not start in AUTO with 2-wire start signal.Contact Independent Authorized Servicing Dealer.
1048VSCF Overload — Unit shuts down during operation.Alternator, AVR or wiring is damaged.Contact Independent Authorized Servicing Dealer.
1049VSCF Overload — Unit shuts down during operation.Generator output is shorted or severely overloaded.Identify and clear the overload, and then restart.
1051VSCF High Battery — Yellow LED illuminated in any state.Voltage supply to the AVR is high.If an external battery charger is in use, contact installing dealer to correct installation. If an external battery charger is NOT in use, contact Independent Authorized Servicing Dealer.
1052VSCF DC Overvoltage — Unit shuts down during operation.The generator was temporarily overloaded; The output was temporarily shorted.Try to restart the unit.
1053VSCF Gate Fault — Unit shuts down during operation or starting.AVR is damaged.Contact Independent Authorized Servicing Dealer.
1054VSCF IGBT Overtemp. — Unit shuts down during operation or starting.Replace AVR filter. Inspect fan.Replace AVR filter. Inspect fan.
1054VSCF IGBT Overtemp. — Unit shuts down during operation or starting.Intake or exhaust air path is blocked.Check intake and exhaust.
1054VSCF IGBT Overtemp. — Unit shuts down during operation or starting.Air leak in AVR enclosure.Contact Independent Authorized Servicing Dealer.
1054VSCF IGBT Overtemp. — Unit shuts down during operation or starting.Engine running too hot.Inspect air intake and exhaust.
1054VSCF IGBT Overtemp. — Unit shuts down during operation or starting.Ambient temperature has risen above 60º F (15.5 °C).Derate the generator output per specifications.
1055VSCF Phase Error — Unit shuts down during starting.An incorrect voltage and frequency has been detected during starting. Alternator damage.Contact Independent Authorized Servicing Dealer.
1055VSCF Phase Error — Unit shuts down during starting.Generator has started into a severe load.Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again.
1055VSCF Phase Error — Unit shuts down during starting.The engine may not be reaching its prescribed speed.Verify stepper motor is moving and linkage is free; Verify stepper motor is plugged in; Verify gas pressure is within specified limits.
1056VSCF Undervoltage — Unit shuts down during operation or starting.The generator output voltage is too low. The load is too large.Remove load and attempt to restart unit.
1056VSCF Undervoltage — Unit shuts down during operation or starting.Alternator or AVR damage.Contact Independent Authorized Servicing Dealer.
1057VSCF Overvoltage — Unit shuts down during operation or starting.The generator has been overloaded.Remove load and attempt to restart unit.
1057VSCF Overvoltage — Unit shuts down during operation or starting.Generator has started into a severe load.Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again.
1058VSCF DC Undervoltage — Unit shuts down during operation or starting.The DPE winding supplies this voltage. Alternator damage.Contact Independent Authorized Servicing Dealer.
1059VSCF Field Loss — Unit shuts down during starting.Unit detects no output voltage while starting. Alternator damage.Contact Independent Authorized Servicing Dealer.
1061VSCF Field Loss — Unit shuts down during operation.Unit detects loss of output voltage while running. Alternator damage.Contact Independent Authorized Servicing Dealer.
1060Big Fan Failure — Unit shuts down during operation.This alarm occurs when the AVR electronics temperature exceeds 70 C. AVR filter faulty.Replace AVR filter.
1060Big Fan Failure — Unit shuts down during operation.Intake or exhaust air path is blocked.Check intake and exhaust.
1060Big Fan Failure — Unit shuts down during operation.Air leak in AVR enclosure.Contact Independent Authorized Servicing Dealer.
1060Big Fan Failure — Unit shuts down during operation.Engine running too hot.Inspect air intake and exhaust.
1060Big Fan Failure — Unit shuts down during operation.Ambient temperature has risen above 60º F (15.5 °C).Derate the generator output per specifications.
1060Big Fan Failure — Unit shuts down during operation.If message is displayed when generator is stopped, also check SMALL fan. Small fan RUNS for 60 minutes after generator is stopped and keeps electronics cool during heat soak.
1065Overfrequency — Unit shuts down during operation.Overload.Remove load and attempt to restart unit.
1065Overfrequency — Unit shuts down during operation.RPM sensor has failed.Contact Independent Authorized Servicing Dealer.
1065Overfrequency — Unit shuts down during operation.Stepper motor problem.Contact Independent Authorized Servicing Dealer.
1066VSCF Speed mismatch — Unit shuts down during Operation or starting.Fuel problem (pressure loss).Check fuel supply and attempt to restart unit.
1066VSCF Speed mismatch — Unit shuts down during Operation or starting.Large overload.Remove load and attempt to restart unit.
1066VSCF Speed mismatch — Unit shuts down during Operation or starting.Throttle or engine problem.Contact Independent Authorized Servicing Dealer.
1070Small fan failure — "Small fan failure" is displayed. If unit was running in AUTO, it will continue to run for one hour to cool electronics without fan.Small fan current incorrect. Fan wiring or mechanical problem.Contact Independent Authorized Servicing Dealer.
1049 VSCFOverload RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Generator output is shorted or severely overloaded. Identify and clear the overload, and then restart.
1051 VSCFHigh Battery YELLOW LED illuminated in any state.Check the LEDs/Screen for alarms. Voltage supply to the AVR is high. If an external battery charger is in use, contact installing dealer to correct installation. If an external battery charger is NOT in use, contact Independent Authorized Servicing Dealer.
1052 VSCFDC Overvoltage RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Probable causes are: 1) The generator was temporarily overloaded. 2) The output was temporarily shorted. Try to restart the unit.
1053 VSCFGate Fault RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. AVR is damaged. Contact Independent Authorized Servicing Dealer.
1055 VSCFPhase Error RED Unit shuts down during starting.Check the LEDs/Screen for alarms. An incorrect voltage and frequency has been detected during starting. Probable causes are: 1) Alternator damage. Contact Independent Authorized Servicing Dealer. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again. 3) The engine may not be reaching its prescribed speed. Proceed as follows: •Verify stepper motor is moving and linkage is free. •Verify stepper motor is plugged in. •Verify gas pressure is within specified limits.
1056 VSCFUndervoltage RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. The generator output voltage is too low. Probable causes are: 1) The load is too large. Remove load and attempt to restart unit. 2) Alternator or AVR damage. Contact Independent Authorized Servicing Dealer.
1057 VSCFOvervoltage RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. Probable causes are: 1) The generator has been overloaded. Remove load and attempt to restart unit. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again.
1058 VSCFDC Undervoltage RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. The DPE winding supplies this voltage. 1) Alternator damage. Contact Independent Authorized Servicing Dealer.
1059 VSCFField Loss RED Unit shuts down during starting.Check the LEDs/Screen for alarms. Unit detects no output voltage while starting. 1) Alternator damage. Contact Independent Authorized Servicing Dealer.
1061 VSCFField Loss RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Unit detects loss of output voltage while running. 1) Alternator damage. Contact Independent Authorized Servicing Dealer.
1066 VSCFSpeed mismatch RED Unit shuts down during Operation or starting.Check the LEDs/Screen for alarms. Probable causes are: 1) Fuel problem (pressure loss). Check fuel supply and attempt to restart unit. 2) Large overload. Remove load and attempt to restart unit. 3) Throttle or engine problem. Contact Independent Authorized Servicing Dealer.

Symptoms & remedies

SymptomCauseRemedy
Low Fuel Level ShutdownFuel level low or unit not sitting level; leaks in fuel tank; fuel level sender or connecting wiring damagedCheck fuel level on the LCD window and verify the unit is sitting level; check for leaks in fuel tank; check the fuel level sender and the connecting wiring for damage and check for continuity between the sender and the engine controller
Low Oil Pressure ShutdownEngine oil level low; oil leaks; loss of oil pressure; oil pressure sender faultCheck engine oil level with the dipstick and add oil if required; visually inspect engine for oil leaks; restart the unit and verify the loss of oil pressure, shutting the engine down immediately if the oil pressure value does not read 5 psi (34 kPa) within five seconds; check oil pressure sender per the troubleshooting section of the engine operator's manual
Low Coolant Level ShutdownCoolant level low; leaks in coolant hoses, engine block or water pump; coolant mixed with engine oilAllow engine to cool; check coolant level in the radiator and add coolant until it is 3/4 in. (2 cm) below the filler neck, then secure the radiator cap; inspect coolant hoses, engine block and water pump for visible leaks; check engine oil to verify no coolant has mixed with it and see the engine operator's manual
High Coolant Temperature ShutdownCoolant level lowCheck coolant level in the overflow jug; restart engine and read the coolant temperature to verify a high coolant temperature shutdown, stopping engine immediately if the coolant temperature is 230°F (110°C) or more; allow engine to cool, add coolant to the overflow jug if it is low and check the level of coolant in the radiator
Low fuel level ShutdownLow fuel levelCheck fuel level in LCD window of controller.
Low fuel level ShutdownUnit not levelConfirm that unit is sitting level to ensure an accurate reading.
Low fuel level ShutdownFuel tank leakingCheck tank for leaks.
Low fuel level ShutdownDamaged fuel sender or wiringCheck for continuity between sender and engine controller. (See Wiring Diagrams.)
Low oil pressure shutdownLow oil levelCheck oil level on dipstick. Add oil, if needed.
Low oil pressure shutdownOil leaking from engineVisually inspect the engine for leaks. Restart unit and verify loss of pressure. Shut down immediately if pressure does not reach 5 psi (34 kPa) within five seconds.
Low oil pressure shutdownOil pressure senderSee engine operator’s manual to identify corrective action.
Low coolant level shutdownLow coolant levelAllow engine to cool, then check coolant level in radiator. Add coolant, if needed.
Low coolant level shutdownCoolant hoses leakingInspect hoses for leaks. Repair or replace as necessary.
Low coolant level shutdownEngine block or water pump leakingVisually inspect for leaks. Verify no coolant has mixed with the engine oil (oil will appear milky). See engine operator’s manual for additional information.
High coolant temperature shutdownLow coolant levelAdd coolant if needed. Allow engine to cool, then check coolant level in radiator. Restart engine and check coolant temperature (on controller). Stop engine immediately if temperature is 210 °F (99 °C) or 230 °F (110 °C).
High coolant temperature shutdownBlockage in radiatorCheck radiator shroud and ducting for blockage and remove any foreign matter.
High coolant temperature shutdownLeakage in coolant hoses, engine block, or water pumpInspect for visible leaks. Check tension of water pump serpentine drive belt.
Overcrank shutdownFuel level lowCheck fuel level in tank.
Overspeed or underspeed shutdownFrequency setting incorrectDisconnect all loads and restart unit. Read frequency (Hz) in the LCD window on controller. Frequency should read 60 Hz.
Engine will not crank.Fuse blown.Correct short circuit condition by replacing 7.5 Amp fuse.
Engine will not crank.Loose, corroded or defective battery cables.Tighten, clean or replace as necessary.*
Engine will not crank.Defective starter contact.Tighten, clean or replace as necessary.*
Engine will not crank.Defective starter motor.Tighten, clean or replace as necessary.*
Engine will not crank.Dead battery.Charge or replace battery.
Engine cranks but will not start.Out of fuel.Replenish fuel / Turn on fuel valve.
Engine cranks but will not start.Defective fuel solenoid (FS).*
Engine cranks but will not start.Defective spark plug(s).Clean, check gap, or replace plug(s).
Engine cranks but will not start.Valve clearance needs adjustment.Adjust valve clearance.
Engine starts hard and runs rough.Air cleaner plugged or damaged.Check / replace air cleaner.
Engine starts hard and runs rough.Defective spark plug(s).Clean, check gap, or replace plug(s).
Engine starts hard and runs rough.Fuel regulator not set.Set fuel regulator.
Engine starts hard and runs rough.Fuel pressure incorrect.Confirm fuel pressure to regulator is 10–12 in. water column (19–22 mm mercury) for LP, and 3.5–7 in. water column (7–13 mm mercury) for natural gas.
Engine starts hard and runs rough.Fuel selector in wrong position.Move selector to correct position.
Generator is set to OFF, but the engine continues to run.Control board wired incorrectly.Repair wiring or replace control board.*
Generator is set to OFF, but the engine continues to run.Defective control board.Replace control board.
No AC output from generator.Main line circuit breaker is in the OFF (or OPEN) position.Reset circuit breaker to ON (or CLOSED).
No AC output from generator.Generator internal failure.*
Unit consumes large amounts of oil.Oil tank is over filled with oil.Adjust oil to proper level.
Unit consumes large amounts of oil.Engine breather defective.*
Unit consumes large amounts of oil.Improper type or viscosity of oil.See Engine Oil Recommendations.
Unit consumes large amounts of oil.Damaged gasket, seal or hose.Check for oil leaks.
Unit running in AUTO but no power in house.Contact Independent Authorized Servicing Dealer if Generator Disconnect circuit breaker is in the ON position.
Unit will not start in AUTO with 2-wire start signal.Check screen for start delay countdown. If the start up delay is greater than expected, contact Independent Authorized Servicing Dealer to adjust from 2 to 1500 seconds.
Generator stalls when large load is supplied.Total load is too big for the generator.Loads must be less than 10 kW or 2 hp when operating under 3600 rpm. Contact installing dealer to correct installation.
Output voltage is low/high.Voltage calibration incorrect.Contact Independent Authorized Servicing Dealer.
Generator does not pull full power.Current calibration incorrect.Contact Independent Authorized Servicing Dealer.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Cross-brand guides for these symptoms

Common questions

Generac MMG35DF4: Big Fan Failure — Unit shuts down during operation — what causes it?

Documented causes: This alarm occurs when the AVR electronics temperature exceeds 70 C. AVR filter faulty.; Intake or exhaust air path is blocked.; Air leak in AVR enclosure.; Engine running too hot.. See the table for the matching fixes.

Generac MMG35DF4: Engine will not crank — what causes it?

Documented causes: Fuse blown.; Loose, corroded or defective battery cables.; Defective starter contact.; Defective starter motor.. See the table for the matching fixes.

Generac MMG35DF4: Engine starts hard and runs rough — what causes it?

Documented causes: Air cleaner plugged or damaged.; Defective spark plug(s).; Fuel regulator not set.; Fuel pressure incorrect.. See the table for the matching fixes.