| Code | Meaning | Cause | Remedy |
|---|---|---|---|
| (000139) | Low oil pressure shutdown | Low oil level | Verify oil level on dipstick. Add oil, if needed. |
| Symptom | Cause | Remedy |
|---|---|---|
| Oil leaking from engine | Visually inspect the engine for leaks. | |
| Oil pressure switch failure | Refer to OEM engine operator’s manual to identify corrective action. | |
| High coolant temperature shutdown | Low coolant level | Add coolant if needed. Allow engine to cool, then check coolant level in radiator. Restart engine and check coolant temperature. Stop engine immediately if coolant temperature is 210°F (99°C) or more. |
| Blockage in radiator | Inspect radiator shroud and ducting for blockage and remove any foreign matter. | |
| Leakage in coolant hoses, engine block, or water pump | Inspect for visible leaks. Verify tension of water pump serpentine drive belt. | |
| Unit cranks, but will not start | Check fuel level in tank. Verify fuel pump operation. Inspect air filter for blockage. | |
| Mast Lights Off, but Ballast Indicators on Control Panel are On. | Light fixture is too hot. Faulty lamp connection. Lamp broken Loose lighting connections Damaged or loose electrical cord | Allow light to cool 10-15 minutes before restarting. Check that the lamp is tight in the socket. Check for broken arc tube or outer lamp jacket, broken or loose components in lamp envelope, or blackening/deposits inside tube. Check the connections inside the mast junction box and each mast light housing/socket. Check the mast electrical cord for damage and check the cord connections inside the control box. |
| Mast Lights Off, and Ballast Indicators on the Control Panel are Off. | Loose lighting connections Generator output incorrect. Low transformer output. | Check the connections inside the control box and inside each ballast box. Check the incoming voltage to the ballast by checking the available voltage on the GFCI receptacle. Incoming voltage should be 120V +/- 5V. If voltage is incorrect, the engine speed may need to be adjusted or generator may require service. The voltage from the transformer should read approximately 400VAC as the light “strikes” (induces an arc), then drop and slowly rise back up to stabilize at 240-260VAC. On hard wired models, remove the mast junction box cover and insert the wire probes into the connector blocks for the light and ground. If proper voltage is not achieved, perform capacitor check to determine if the capacitor or coil needs to be replaced. |
| Mast Lights On But the Light Output is Low | Fixture and/or lens is dirty. Lamp worn due to normal use Damaged or loose electrical connections Generator output incorrect. Low transformer output | Clean reflective surface inside fixture and both inside and outside surface of glass lens. Use mild soap and water to clean lens. Other chemicals may have an adverse effect on the glass. Replace lamp. Check the mast coil cord, mast junction box and mast light connections. Check the incoming voltage to the ballast. Incoming voltage should be 120V +/-5V. If the voltage is incorrect, the engine speed may need to be adjusted or the generator may require service. The voltage from the transformer should read approximately 400VAC as the light “strikes” (induces an arc), then drop and slowly rise back up to stabilize at 240-260VAC. On hard wired models, remove the mast junction box cover and insert the wire probes into the connector blocks for the light and ground. If proper voltage is not achieved, perform capacitor check to determine if the capacitor or coil needs to be replaced. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.
Documented causes: Low oil level. See the table for the matching fixes.
Documented causes: Visually inspect the engine for leaks.. See the table for the matching fixes.
Documented causes: Low coolant level. See the table for the matching fixes.