Generac In Line troubleshooting: 15 fault codes and symptom-cause-remedy entries from the manufacturer's own service documentation.

Generac In Line — full specs, parts & maintenance.

All Generac fault codes →

Troubleshooting

15

Fault codes

CodeMeaning
Safety 001Not stated

Symptoms & remedies

SymptomCauseRemedy
Engine won’t crank.1. 15 amp fuse blown. 2. Loose or corroded or defective battery cables. 3. Defective starter contactor. 4. Defective starter motor. 5. Dead or Defective Battery. 6. 5 amp fuse blown.1. Replace fuse. 2. Tighten, clean or replace battery cables as necessary. 3. Replace contactor.* 4. Replace starter motor.* 5. Remove, change or replace battery. 6. Replace fuse.*
Engine cranks but won't start1. Out of fuel. 2. Fuel solenoid (FS) is defective 3. Open Wire #14A from Engine Control circuit board. 4. Spark plugs defective. 5. Door on tank not closed.1. Replenish fuel. 2. Replace solenoid.* 3. Reconnect wire. 4. Clean, regap or replace plugs. 5. Close door on tank.
Engine starts hard, runs rough.1. Flame arrestor (air cleaner) plugged or damaged. 2. Plugged fuel line. 3. Defective spark plugs. 4. Fuel pressure incorrect.1. Clean or replace as needed. 2. Unclog fuel line. 3. Clean, regap or replace plugs. 4. Confirm fuel pressure to regulator is as recommended in SPECIFICATIONS.
Engine oil level is low.Check oil and add oil as needed.
Engine is overheated.Check cooling system for leaks.
Defective Low Oil Pressure SwitchReplace switch.*
Defective Coolant Temperature SwitchReplace switch.*
Defective Control Module circuit boardReplace board.*
Coolant Level is Low.Repair leak - Add coolant.
Defective AUTO/OFF/MANUAL switchReplace switch.*
Open/disconnected wire #15A between AUTO/OFF/MANUAL switch and Control Module circuit board.Reconnect/close wire.
Engine starts then shuts down.Defective Control Module circuit board *Contact the nearest Authorized Dealer for assistance.
AUTO/OFF/MANUAL Switch at OFF, engine continues to run1. Check main line circuit breaker. 2. Check circuit breaker & fuses. 3. Transfer switch set to NORMAL position 4. Generator internal failure. 5. Thermal circuit breaker open.
No AC output from generator.1. Reset to ON or CLOSED. 2. Reset and replace, if necessary. 3. Set to GENERATOR position. 4. Auto-reset - Wait 5 min. and attempt restart.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Cross-brand guides for these symptoms

Common questions

Generac In Line: Engine won’t crank — what causes it?

Documented causes: 1. 15 amp fuse blown. 2. Loose or corroded or defective battery cables. 3. Defective starter contactor. 4. Defective starter motor. 5. Dead or Defective Battery. 6. 5 amp fuse blown.. See the table for the matching fixes.

Generac In Line: Engine cranks but won't start — what causes it?

Documented causes: 1. Out of fuel. 2. Fuel solenoid (FS) is defective 3. Open Wire #14A from Engine Control circuit board. 4. Spark plugs defective. 5. Door on tank not closed.. See the table for the matching fixes.

Generac In Line: Engine starts hard, runs rough — what causes it?

Documented causes: 1. Flame arrestor (air cleaner) plugged or damaged. 2. Plugged fuel line. 3. Defective spark plugs. 4. Fuel pressure incorrect.. See the table for the matching fixes.