Generac 15 kW EcoGen Troubleshooting

Generac 15 kW EcoGen troubleshooting: 70 fault codes and 60 symptom-cause-remedy entries from the manufacturer's own service documentation.

Generac 15 kW EcoGen — full specs, parts & maintenance.

All Generac fault codes →

Troubleshooting

130

Fault codes

CodeMeaningCauseRemedy
HIGH TEMPERATUREUnit shuts down during operation — LED redCheck the LEDs / screen for alarmsCheck ventilation around the generator, intake, exhaust, and rear of generator. If no obstructions are present, contact an IASD.
OVERLOAD REMOVE LOADUnit shuts down during operation — LED redCheck the LEDs / screen for alarmsClear alarm and remove household loads from the generator. Put in AUTO and restart.
RPM SENSE LOSSUnit was running and shut down, attempts to restart — LED redCheck the LEDs / screen for alarmsClear alarm and remove household loads from the generator. Put into AUTO and restart. If generator does not start, contact an IASD.
NOT ACTIVATEDUnit will not start in AUTO with remote start signal — LED noneCheck if screen says unit not activatedRefer to “Activation” in installation manual.
LOW OIL PRESSUREUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsCheck oil level and add oil as needed. If oil level is correct, contact an IASD.
RPM SENSE LOSSUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsClear alarm. Using the control panel, check the battery by navigating to the BATTERY MENU option from the MAIN MENU. If battery condition displays GOOD, contact an IASD. If control panel displays CHECK BATTERY, replace the battery.
OVERCRANKUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsCheck fuel line shutoff valve is ON. Clear alarm. Start the unit in MANUAL. If it does not start, or starts and runs rough, contact an IASD.
LOW VOLTS REMOVE LOADUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsClear alarm and remove household loads from the generator. Put in AUTO and restart.
FUSE PROBLEMUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsCheck the 7.5 amp fuse. If it is blown, replace it with an ATO 7.5 amp fuse. If the fuse is intact, contact an IASD.
OVERSPEEDUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsContact an IASD.
UNDERVOLTAGEUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsContact an IASD.
UNDERSPEEDUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsContact an IASD.
STEPPER OVERCURRENTUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsContact an IASD.
MISWIREUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsContact an IASD.
OVERVOLTAGEUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsContact an IASD.
LOW BATTERYYellow LED illuminated in any stateCheck the screen for additional informationClear alarm. Using the control panel, check the battery by navigating to the BATTERY MENU option from the MAIN MENU. If battery condition displays GOOD, contact an IASD. If control panel displays CHECK BATTERY, replace the battery.
BATTERY PROBLEMYellow LED illuminated in any stateCheck the screen for additional informationContact an IASD.
CHARGER WARNINGYellow LED illuminated in any stateCheck the screen for additional informationContact an IASD.
SERVICE AYellow LED illuminated in any stateCheck the screen for additional informationPerform SERVICE A maintenance. Press ENTER to clear.
SERVICE BYellow LED illuminated in any stateCheck the screen for additional informationPerform SERVICE B maintenance. Press ENTER to clear.
INSPECT BATTERYYellow LED illuminated in any stateCheck the screen for additional informationInspect battery. Press ENTER to clear.
1048VSCF Overload — Unit shuts down during operation. LED redAlternator, AVR or wiring is damagedContact servicing dealer.
1049VSCF Overload — Unit shuts down during operation. LED redGenerator output is shorted or severely overloadedIdentify and clear the overload, and then restart.
1051VSCF High Battery — Yellow LED illuminated in any stateVoltage supply to the AVR is highIf an external battery charger is in use, contact installing dealer to correct installation. If an external battery charger is NOT in use, contact servicing dealer.
1052VSCF DC Overvoltage — Unit shuts down during operation. LED redThe generator was temporarily overloaded; The output was temporarily shortedTry to restart the unit.
1053VSCF Gate Fault — Unit shuts down during operation or starting. LED redAVR is damagedContact servicing dealer.
1055VSCF Phase Error — Unit shuts down during starting. LED redAn incorrect voltage and frequency has been detected during starting. Alternator damage. Contact servicing dealer; Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again; The engine may not be reaching its prescribed speedContact servicing dealer; Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again; Verify stepper motor is moving and linkage is free; Verify stepper motor is plugged in; Verify gas pressure is within specified limits
1056VSCF Undervoltage — Unit shuts down during operation or starting. LED redThe generator output voltage is too low. The load is too large. Remove load and attempt to restart unit; Alternator or AVR damage. Contact servicing dealerRemove load and attempt to restart unit; Contact servicing dealer
1057VSCF Overvoltage — Unit shuts down during operation or starting. LED redThe generator has been overloaded. Remove load and attempt to restart unit; Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit againRemove load and attempt to restart unit; Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again
1058VSCF DC Undervoltage — Unit shuts down during operation or starting. LED redThe DPE winding supplies this voltage. Alternator damage. Contact servicing dealerContact servicing dealer.
1059VSCF Field Loss — Unit shuts down during starting. LED redUnit detects no output voltage while starting. Alternator damage. Contact servicing dealerContact servicing dealer.
1061VSCF Field Loss — Unit shuts down during operation. LED redUnit detects loss of output voltage while running. Alternator damage. Contact servicing dealerContact servicing dealer.
1065Overfrequency — Unit shuts down during operation. LED redOverload. Remove load and attempt to restart unit; RPM sensor has failed. Contact servicing dealer; Stepper motor problem. Contact servicing dealerRemove load and attempt to restart unit; Contact servicing dealer
1066VSCF Speed mismatch — Unit shuts down during Operation or starting. LED redFuel problem (pressure loss). Check fuel supply and attempt to restart unit; Large overload. Remove load and attempt to restart unit; Throttle or engine problem. Contact servicing dealerCheck fuel supply and attempt to restart unit; Remove load and attempt to restart unit; Contact servicing dealer
1055 VSCF Phase ErrorUnit shuts down during starting.Check the LEDs/Screen for alarms. An incorrect voltage and frequency has been detected during starting. Probable causes are: 1) Alternator damage. Contact servicing dealer. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again. 3) The engine may not be reaching its prescribed speed. Proceed as follows: • Verify stepper motor is moving and linkage is free. • Verify stepper motor is plugged in. • Verify gas pressure is within specified limits.
1061 VSCF Field LossUnit shuts down during operation.Check the LEDs/Screen for alarms. Unit detects loss of output voltage while running. Probable causes are: 1) Alternator damage. Contact servicing dealer.
HIGH TEMPERATUREUnit shuts down during operation.Check the LEDs/Screen for alarms.Check ventilation around the intake, exhaust and rear of generator. Contact serving dealer if no obstruction is found.
OVERLOAD REMOVE LOADUnit shuts down during operation.Check the LEDs/Screen for alarms.Clear alarm and remove household loads from the generator. Put back in AUTO and restart.
RPM SENSE LOSSUnit was running and shuts down, attempts to restart.Check the LEDs/Screen for alarms.Clear alarm and remove household loads from the generator. Put back in AUTO and restart. If problem returns, contact servicing dealer to investigate possible fuel issue.
NOT ACTIVATEDUnit will not start in AUTO with 2-wire start signal.See if screen says unit not activated.Refer to activation section in Owner’s Manual.
LOW OIL PRESSUREUnit will not start in AUTO with 2-wire start signal.Check the LEDs/Screen for alarms.Check oil level. Add oil per Owner’s Manual. Contact servicing dealer if oil level is correct.
RPM SENSE LOSSUnit will not start in AUTO with 2-wire start signal.Check the LEDs/Screen for alarms.Clear alarm. Navigate to the BATTERY MENU on the control pad LCD. Contact servicing dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
OVERCRANKUnit will not start in AUTO with 2-wire start signal.Check the LEDs/Screen for alarms.Check fuel line shutoff valve is in the ON position. Clear alarm. Attempt to start the unit in MANUAL. If it does not start or starts and runs rough, contact servicing dealer.
LOW VOLTS REMOVE LOADUnit will not start in AUTO with 2-wire start signal.Check the LEDs/Screen for alarms.Clear alarm and remove household loads from the generator. Set back to AUTO and restart.
FUSE PROBLEMUnit will not start in AUTO with 2-wire start signal.Check the LEDs/Screen for alarms.Check ATO 7.5 Amp fuse. Replace with same type fuse if bad. Contact servicing dealer if fuse is good.
OVERSPEEDUnit will not start in AUTO with 2-wire start signal.Check the LEDs/Screen for alarms.Contact servicing dealer.
UNDER VOLTAGEUnit will not start in AUTO with 2-wire start signal.Check the LEDs/Screen for alarms.Contact servicing dealer.
UNDERSPEEDUnit will not start in AUTO with 2-wire start signal.Check the LEDs/Screen for alarms.Contact servicing dealer.
STEPPER OVERCURRENTUnit will not start in AUTO with 2-wire start signal.Check the LEDs/Screen for alarms.Contact servicing dealer.
MISWIREUnit will not start in AUTO with 2-wire start signal.Check the LEDs/Screen for alarms.Contact servicing dealer.
OVERVOLTAGEUnit will not start in AUTO with 2-wire start signal.Check the LEDs/Screen for alarms.Contact servicing dealer.
LOW BATTERYYellow LED illuminated in any state.Check screen for additional information.Clear alarm. Navigate to the BATTERY MENU on the control pad LCD. Contact servicing dealer if battery is GOOD. Replace battery If CHECK BATTERY is displayed.
BATTERY PROBLEMYellow LED illuminated in any state.Check screen for additional information.Contact servicing dealer.
CHARGER WARNINGYellow LED illuminated in any state.Check screen for additional information.Contact servicing dealer
SERVICE AYellow LED illuminated in any state.Check screen for additional information.Perform SCHEDULE A maintenance. Press ENTER to clear.
SERVICE BYellow LED illuminated in any state.Check screen for additional information.Perform SCHEDULE B maintenance. Press ENTER to clear.
INSPECT BATTERYYellow LED illuminated in any state.Check screen for additional information.Inspect battery. Press ENTER to clear.
1048VSCF Overload — Unit shuts down during operation.Alternator, AVR or wiring is damaged.Contact servicing dealer.
1049VSCF Overload — Unit shuts down during operation.Generator output is shorted or severely overloaded.Identify and clear the overload, and then restart.
1051VSCF High Battery — Yellow LED illuminated in any state.Voltage supply to the AVR is high.If an external battery charger is in use, contact installing dealer to correct installation. If an external battery charger is NOT in use, contact servicing dealer.
1052VSCF DC Overvoltage — Unit shuts down during operation.The generator was temporarily overloaded; The output was temporarily shorted.Try to restart the unit.
1053VSCF Gate Fault — Unit shuts down during operation or starting.AVR is damaged.Contact servicing dealer.
1055VSCF Phase Error — Unit shuts down during starting.An incorrect voltage and frequency has been detected during starting. Probable causes are: Alternator damage. Contact servicing dealer.; Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again.; The engine may not be reaching its prescribed speed. Proceed as follows: Verify stepper motor is moving and linkage is free. Verify stepper motor is plugged in. Verify gas pressure is within specified limits.
1056VSCF Undervoltage — Unit shuts down during operation or starting.The generator output voltage is too low. Probable causes are: The load is too large. Remove load and attempt to restart unit.; Alternator or AVR damage. Contact servicing dealer.
1057VSCF Overvoltage — Unit shuts down during operation or starting.The generator has been overloaded. Remove load and attempt to restart unit.; Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again.
1058VSCF DC Undervoltage — Unit shuts down during operation or starting.The DPE winding supplies this voltage. Alternator damage.Contact servicing dealer.
1059VSCF Field Loss — Unit shuts down during starting.Unit detects no output voltage while starting. Alternator damage.Contact servicing dealer.
1061VSCF Field Loss — Unit shuts down during operation.Unit detects loss of output voltage while running. Alternator damage.Contact servicing dealer.
1065Overfrequency — Unit shuts down during operation.Overload. Remove load and attempt to restart unit.; RPM sensor has failed. Contact servicing dealer.; Stepper motor problem. Contact servicing dealer.
1066VSCF Speed mismatch — Unit shuts down during Operation or starting.Fuel problem (pressure loss). Check fuel supply and attempt to restart unit.; Large overload. Remove load and attempt to restart unit.; Throttle or engine problem. Contact servicing dealer.

Symptoms & remedies

SymptomCauseRemedy
Engine will not crankBlown fuseCorrect short circuit condition by replacing 7.5 amp fuse in generator control panel. Contact an Independent Authorized Service Dealer (IASD) if fuse continues to blow.
Engine will not crankLoose, corroded, or defective battery cablesTighten, clean, or replace as necessary.
Engine will not crankDefective starter contactContact an IASD for assistance.
Engine will not crankDefective starter motorContact an IASD for assistance.
Engine will not crankDischarged batteryCharge or replace battery.
Engine cranks but will not startNo fuelReplenish fuel / turn on fuel valve.
Engine cranks but will not startDefective fuel solenoid (FS)Contact an IASD for assistance.
Engine cranks but will not startOpen Wire 14 from controllerContact an IASD for assistance.
Engine cranks but will not startDefective spark plug(s)Clean; check gap; replace plug(s) if necessary.
Engine cranks but will not startValve clearance out of adjustmentReset valve clearance.
Engine cranks but will not startFuel pressure too highVerify proper fuel pressure.
Engine starts hard and runs roughAir cleaner plugged or damagedCheck and clean air cleaner.
Engine starts hard and runs roughDefective spark plug(s)Clean; check gap; replace plug(s) as needed.
Engine starts hard and runs roughIncorrect fuel pressureConfirm fuel pressure to regulator is 10–12 in water column (19–22 mm Hg) for LP, and 3.5–7.0 in water column (9–13 mm Hg) for natural gas.
Engine starts hard and runs roughFuel selector in wrong positionTurn fuel conversion valve to correct position.
Engine starts hard and runs roughValve(s) out of adjustmentAdjust valve clearance.
Engine starts hard and runs roughInternal engine issueContact an IASD for assistance.
Generator is set to OFF, but the engine continues to runController wired incorrectlyContact an IASD for assistance.
Generator is set to OFF, but the engine continues to runDefective control boardContact an IASD for assistance.
No AC output from generatorMain line circuit breaker (MLCB) (generator disconnect) is OFF (OPEN)Reset generator disconnect to ON (CLOSED).
No AC output from generatorGenerator internal failureContact an IASD for assistance.
No AC output from generatorEngine may be warming up. Refer to Cold Smart StartCheck the controller screen to verify status.
No transfer to generator power after startupMLCB (generator disconnect) is OFF (OPEN)Reset generator disconnect to ON (CLOSED).
No transfer to generator power after startupEngine may be warming up. Refer to Cold Smart StartCheck the controller screen to verify status.
Unit consumes large amounts of oilExcessive engine oilAdjust oil to proper level.
Unit consumes large amounts of oilDefective engine breatherContact an IASD for assistance.
Unit consumes large amounts of oilImproper type or viscosity of oilSee Engine Oil Requirements.
Unit consumes large amounts of oilDamaged gasket, seal, or hoseCheck for oil leaks.
Unit consumes large amounts of oilRestricted air filterReplace air filter.
Unit running in AUTO but no power at L1 and L2 — LED flashing greenCheck MLCBCheck MLCB. If it is ON, contact an IASD.
Unit will not start in AUTO with remote start signal — LED greenCheck screen for start delay countdownIf the startup delay is greater than expected, contact an IASD to adjust.
Generator stalls when large load is suppliedTotal load is too big for the generator. Loads must be less than 10 kW or 2 hp when operating under 3600 rpmContact installing dealer to correct installation.
Output voltage is low/highVoltage calibration incorrectContact servicing dealer.
Generator does not pull full powerCurrent calibration incorrectContact servicing dealer.
Engine will not crank.Fuse blown.Correct short circuit condition by replacing 7.5 Amp fuse.
Engine will not crank.Loose, corroded or defective battery cables.Tighten, clean or replace as necessary.*
Engine will not crank.Defective starter contact.Tighten, clean or replace as necessary.*
Engine will not crank.Defective starter motor.Tighten, clean or replace as necessary.*
Engine will not crank.Dead Battery.Charge or replace battery.
Engine cranks but will not start.Out of fuel.Replenish fuel / Turn on fuel valve.
Engine cranks but will not start.Defective fuel solenoid (FS).*
Engine cranks but will not start.Defective spark plug(s).Clean, re-gap or replace plug(s).
Engine cranks but will not start.Valve clearance needs adjustment.Adjust valve clearance.
Engine starts hard and runs rough.Air cleaner plugged or damaged.Check / replace air cleaner.
Engine starts hard and runs rough.Defective spark plug(s).Clean, re-gap or replace plug(s).
Engine starts hard and runs rough.Fuel regulator not set.Set fuel regulator.
Engine starts hard and runs rough.Fuel pressure incorrect.Confirm fuel pressure to regulator is 10-12” water column (19-22mm mercury) for LP, and 3.5 - 7” water column (9-13mm mercury) for natural gas.
Engine starts hard and runs rough.Fuel selector in wrong position.Move selector to correct position.
Generator is set to OFF, but the engine continues to run.Control board wired incorrectly.Repair wiring or replace control board.*
Generator is set to OFF, but the engine continues to run.Defective control board.Replace control board.
No AC output from generator.Main line circuit breaker is in the OFF (or OPEN) position.Reset circuit breaker to ON (or CLOSED).
No AC output from generator.Generator internal failure.*
Unit consumes large amounts of oil.Oil tank is over filled with oil.Adjust oil to proper level.
Unit consumes large amounts of oil.Engine breather defective.*
Unit consumes large amounts of oil.Improper type or viscosity of oil.See “Engine Oil Recommendations.”
Unit consumes large amounts of oil.Damaged gasket, seal or hose.Check for oil leaks.
Unit running in AUTO but no power in house.Generator Disconnect circuit breaker.Contact servicing dealer if Generator Disconnect circuit breaker is in the ON position.
Generator stalls when large load is supplied.Total load is too big for the generator.Loads must be less than 10 kW or 2 hp when operating under 3600 rpm. Contact installing dealer to correct installation.
Output voltage is low/high.Voltage calibration incorrect.Contact servicing dealer.
Generator does not pull full power.Current calibration incorrect.Contact servicing dealer.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Cross-brand guides for these symptoms

Common questions

Generac 15 kW EcoGen: Yellow LED illuminated in any state — what causes it?

Documented causes: Check the screen for additional information; Check screen for additional information.. See the table for the matching fixes.

Generac 15 kW EcoGen: Unit will not start in AUTO with 2-wire start signal — what causes it?

Documented causes: See if screen says unit not activated.; Check the LEDs/Screen for alarms.. See the table for the matching fixes.

Generac 15 kW EcoGen: Engine starts hard and runs rough — what causes it?

Documented causes: Air cleaner plugged or damaged; Defective spark plug(s); Incorrect fuel pressure; Fuel selector in wrong position. See the table for the matching fixes.