Home› Troubleshooting›Cummins/Onan MDKAE

Cummins/Onan MDKAE Troubleshooting

Cummins/Onan MDKAE troubleshooting: 43 symptom-cause-remedy entries from the manufacturer's own service documentation.

Cummins/Onan MDKAE — full specs, parts & maintenance.

All Cummins/Onan fault codes →

Troubleshooting

43

Symptoms & remedies

SymptomCauseRemedy
Engine does not crankOpen circuit breaker CB1, CB2 or CB4Check to see if breaker is accidentally tripped; Check and correct fault conditions that might trip breakers: CB1: check shorts to ground on/near glow plug circuits; CB2: check and correct fault conditions sensed by engine fault sensors: S2: high engine temperature, S3: low coolant level, S4: low oil pressure, S5: high exhaust temperature; CB2: check possible shorted fault sensors S1, S2, S3, S4; CB4: check K7 stop solenoid for adjustment
Engine does not crankNo B+ voltage to starterCheck B+ and ground connections at battery and grounding point on engine; Check battery cables per Checkout B (Section 3 of manual); Check B+ voltage while cranking at SW terminal on starter (TB2-11): is there voltage while pressing Start switch? Yes: problem is in starter or solenoid; No: problem is in control circuit
Engine does not crankStarter is not functionalRemove starter from genset, check and replace if necessary
Engine does not crankBattery is not functionalCheck battery per Checkout A (Section 3 of manual) and recharge or replace; Check battery charger operation per Checkout C (Section 3)
Engine does not crankStart relay K1 is not functionalCheck relay per Checkout D (Section 3), replace if bad; Check K7 stop solenoid for adjustment
Engine cranks but does not startFuel is not getting to the engineCheck fuel pump per Checkout H (Section 3); Place meter on fuel pump terminal and press Start switch: is voltage reaching fuel pump?; Test fuel tank level, shutoff valves, fuel lines and connections, fuel filters, injection pump; Air in fuel lines: prime fuel system
Engine cranks but does not startGlow plugs not operating correctlyCheck/replace individual glow plugs per instructions in Engine Manual; Place meter on glow plug terminal and press Preheat switch: is voltage reaching glow plug?; Test K5 glow plug relay per Checkout E (Section 3); Test continuity of K5 circuit; Test Start/Stop-Preheat switch per Checkout G (Section 3)
Engine cranks but does not startFuel shutoff solenoid not operating correctlyPlace meter on fuel solenoid terminal and press Start switch: is voltage reaching fuel solenoid?; Test fuel solenoid circuit for continuity through B+; Disconnect fuel solenoid from circuit, test per Checkout F (Section 3). Adjust/replace as necessary.
Engine starts but stops after several secondsFault conditions cause fault breaker CB2 to openCB2: check and correct fault conditions sensed by engine fault sensors: S2: high engine temperature: check water pump operation; S3: low coolant level; S4: low oil pressure; S5: high exhaust temperature; Check possible overspeed conditions; Engine speed set too high: reset to 1500 or 1800 rpm according to instructions in Section 4 of manual; Voltage regulator board 50/60 Hz switch is set at 50 Hz while governor lever is set at 60 Hz: both settings must be the same; Check all B+ wiring for shorts to ground
Engine starts but stops after several secondsFuel pump is stopped or intermittentCheck fuel pump per Checkout H in next section of manual: replace if necessary; Check fuel pump circuit for continuity
Engine starts but stops after several secondsAir in fuel linePrime fuel system (press S1 to the STOP position)
Engine starts and runs but remains running only while start switch is heldIf there is AC output from the set: K4 relay may not be changing stateRemove K4, check per Checkout E (Section 3): replace if necessary; Check K4 wiring for continuity
Engine starts and runs but remains running only while start switch is heldIf there is no AC output from the set: generator/voltage regulator may be at fault (not control system)Check generator/voltage regulator per procedures in Sections 5 and 6 of manual
No AC output voltage at rated engine RPMLoad circuit breakers not closedClose circuit breakers, or replace if bad. If voltage is unstable, high or low, or causes breaker to trip, see Flow Charts B or C.
No AC output voltage at rated engine RPMResidual voltage across L1 and L2 not 14 VAC ± 5 VAC (TEST [A])Flash exciter field per TEST [B]. Does generator output voltage build up?
No AC output voltage at rated engine RPMAfter flashing field, output voltage does not build upDisconnect J2/P2 connection to voltage regulator. Is residual voltage across L1 and L2 14 VAC ± 5 VAC now?
No AC output voltage at rated engine RPMResidual voltage not present with J2/P2 disconnectedGenerator stator is OK. Check exciter rotor and stator wiring per TESTS [F] and [G]. Check exciter field wiring for shorts per TEST [J]. Replace bad wiring. Check lead continuity per TEST [J]. Check diodes CR1 through CR6 on rotor per TEST [E]. Replace if bad. Check exciter rotor winding per TEST [G]. Replace if bad. Check generator rotor winding per TEST [I]. Replace if bad. Check generator stator windings per TEST [H]. Replace if bad.
No AC output voltage at rated engine RPMResidual voltage present with J2/P2 disconnectedIs exciter field voltage at (J2/P2 pins 8 and 1) approximately 6.5 VAC (60 Hz sets) or volts ± 10 VAC? Yes: AVR should be OK. Check exciter rotor winding per TEST [G]. Replace if bad. No: Check exciter field wiring for shorts per TEST [J]. Check voltage regulator per TEST [C].
Unstable voltage, engine speed stableBroken wires or loose connections on voltage regulator assemblyCheck wiring harness from regulator assembly to end bell per TEST [J]. Check OK? Yes: Replace the voltage regulator per procedure (D). No: Repair as required. Repair wiring or replace as required.
Unstable voltage, engine speed stableEngine not running at correct RPMSet RPM per instructions in appropriate engine manual.
Unstable voltage, engine speed stableAdjustment of Voltage Adjust control on the regulator board does not result in correct output voltageSet control per Voltage Adjustment [K].
Unstable voltage, engine speed stableVoltage regulator connections not secureCheck/retighten/replace voltage regulator connections.
Unstable voltage, engine speed stableGenerator output leads not properly connectedSee TEST [L]. Replace the voltage regulator per procedure [D].
Unbalanced generator output voltageOutput still unbalanced with load removed at generator terminalsAre generator leads connected and grounded properly? See Test [L]. Is generator stator winding continuous per TEST [H]? Yes: Replace stator assembly. No: Check for correct grounding of generator and load. Correct as necessary.
Unbalanced generator output voltageOutput balanced with load removed (load fault)Check load for ground faults and correct as necessary.
Engine does not crank from remote panelEmergency Stop Switch OFFPush ON.
Engine does not crank from remote panel“Check Generator” or “Check Engine” FaultService the fault as necessary and push fault reset button in. See “CHECK ENGINE” FAULT SHUTDOWN or “CHECK GENERATOR” FAULT SHUTDOWN.
Engine does not crank from remote panelFaulty remote circuitTry starting at the genset control panel. If the genset starts, have the remote circuit repaired as necessary.
Engine does not crank from genset panelEmergency Stop Switch OFFPush ON.
Engine does not crank from genset panel“Check Generator” or “Check Engine” FaultService the fault as necessary and push fault reset button in. See “CHECK ENGINE” FAULT SHUTDOWN or “CHECK GENERATOR” FAULT SHUTDOWN.
Engine does not crank from genset panelCranking voltage too lowClean and tighten or replace the positive (+) and negative (-) battery cable connectors and cables at the battery and the genset; Recharge or replace the battery. Specific gravity for a fully charged battery is approximately 1.260 at 80° F (27° C).
Engine cranks but does not startEngine not getting fuelOpen any closed shutoff valve; Check fuel level and refill as necessary; Prime the fuel system (p. 25); Check for fuel (air) leaks at all fittings and tighten as necessary; Replace the fuel filter (p. 24).
Engine cranks but does not startBlocked air inletService as necessary.
Engine cranks but does not startLow engine temperaturePlug in, repair or install engine coolant and engine oil heaters; Replace the engine oil if it is not of the recommended viscosity for the ambient temperature.
Engine cranks but does not startCranking voltage too lowClean and tighten or replace the positive (+) and negative (-) battery cable connectors and cables at the battery and the genset; Recharge or replace the battery. Specific gravity for a fully charged battery is approximately 1.260 at 80° F (27° C).
“Check Engine” Fault ShutdownLow engine oil pressureCheck engine oil level, repair any leaks and fill to the proper level (p. 18).
“Check Engine” Fault ShutdownHigh engine temperatureCheck engine coolant level, repair any leaks and fill to the proper level (p. 19); Check V-belt tension (p. 21); Clean and service the cooling system as required to restore full cooling capacity (p. 19).
“Check Engine” Fault ShutdownHigh exhaust temperatureOpen the sea cock; Remove any blockage in the sea water strainer; Prime the sea water pump (p. 23); Replace the sea water pump impeller (p. 23); Clean seaweed and pump debris from heat exchanger (p. 23); Remove blockage covering the sea water hull strainer.
“Check Generator” Fault ShutdownGenerator overload.Run with less load.
Engine lacks power or is unstableInadequate fuel deliveryCheck for fuel (air) leaks at all fittings and tighten as necessary; Replace the fuel filter (p. 24).
Engine lacks power or is unstableContaminated fuelConnect the fuel lift pump to a container of fuel of known quality. Replace the contents of the fuel supply tank if there is a noticeable difference in performance.
No output voltageA line circuit breaker is Off.Find out why the circuit breaker was turned Off, make sure it is safe to reconnect power, and then throw the circuit breaker On.
No output voltageA line circuit breaker has Tripped.Shut down the genset and have service performed as necessary to clear the short circuit or ground fault that caused tripping. Then Reset the circuit breaker and start the genset.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Cross-brand guides for these symptoms

Common questions

Cummins/Onan MDKAE: Engine cranks but does not start — what causes it?

Documented causes: Fuel is not getting to the engine; Glow plugs not operating correctly; Fuel shutoff solenoid not operating correctly; Engine not getting fuel. See the table for the matching fixes.

Cummins/Onan MDKAE: Engine does not crank — what causes it?

Documented causes: Open circuit breaker CB1, CB2 or CB4; No B+ voltage to starter; Starter is not functional; Battery is not functional. See the table for the matching fixes.

Cummins/Onan MDKAE: No AC output voltage at rated engine RPM — what causes it?

Documented causes: Load circuit breakers not closed; Residual voltage across L1 and L2 not 14 VAC ± 5 VAC (TEST [A]); After flashing field, output voltage does not build up; Residual voltage not present with J2/P2 disconnected. See the table for the matching fixes.