Home TroubleshootingCummins/Onan C12 D6

Cummins/Onan C12 D6 Troubleshooting

Cummins/Onan C12 D6 troubleshooting: 17 fault codes and symptom-cause-remedy entries from the manufacturer's own service documentation.

Cummins/Onan C12 D6 — full specs, parts & maintenance.

All Cummins/Onan fault codes →

Troubleshooting

17

Fault codes

CodeMeaning
59High AC voltage shutdown
27Low AC voltage shutdown
81 uUnder frequency shutdown
81 oOver frequency shutdown/warning
51High Current warning/shutdown

Symptoms & remedies

SymptomCauseRemedy
Battery voltage warningStatus of battery charging system (failure)
Emergency stop signal is receivedThe generator set immediately shuts down and cannot run or crank with the E-stop switch engaged.
Time delay of 0-600 seconds prior to shutdown after signal to stop in normal operation modesDefault for both time delay periods is 0 seconds.
Undervoltage sensor pickup and dropout adjustable from 85-100% and 75-98%Dropout adjustable delay from 0.1-30 sec.
Overvoltage sensor dropout adjustable from 105-135% of nominalDropout adjustable delay from 0.5-120 sec.
Over/under frequency sensor underfrequency sensing pickup and dropout adjustable from 85-100% and 70-85%Dropout adjustable delay from 0.1-15 sec.
Over/under frequency sensor overfrequency sensing dropout adjustable from 105-115% of nominalDropout adjustable delay from 0.1-15 sec.
Time delay start and stop (cooldown) configurable for time delay of 0-300 seconds prior to starting after receiving a remote start signalControl provides retransfer time delays including time delay emergency to normal (0-1800 sec), programmed transition delay (0-600 sec), and time delay engine cooldown (0-3600 sec).
Low lube oil pressure warning/shutdownLevel is pre-set to match the capabilities of the engine used. Control includes time delays to prevent nuisance shutdown signals.
High coolant temperature warning/shutdownLevel is pre-set to match the capabilities of the engine used. Control includes time delays to prevent nuisance shutdown signals.
Low coolant temperature warningIndicates that engine temperature may not be high enough for 1 min. and start or proper load acceptance.
Sensor failure indicationLogic is provided on the base control to detect analog sensor or interconnecting wiring failures.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Common questions

Cummins/Onan C12 D6: Battery voltage warning — what causes it?

Documented causes: Status of battery charging system (failure). See the table for the matching fixes.