Home›Repair guides›Wacker Neuson›Preparing for Automatic/Remote Start-Up (Deep Sea)

Wacker Neuson G 25 — Preparing for Automatic/Remote Start-Up (Deep Sea)

Operation · Remote start circuit

For the Wacker Neuson G 25, from the Wacker Neuson owner's manual.

Applies to: Wacker Neuson G 25

Before you start

  • Verify remote switch contacts are OPEN before pressing AUTO mode.

Procedure

  1. Attach a jumper wire between the two remote run terminals.
  2. Set genset controller power switch to ON.
  3. Press the AUTO mode button.
  4. Wait for engine to crank, start, and run.
  5. Press Stop/Reset to stop the engine.
  6. Remove the jumper wire.
  7. Leave power switch ON and close main circuit breaker.
  8. Press AUTO mode button.
  9. Secure generator by closing and locking all doors.

Tools required

  • Jumper wire (minimum 16-gauge insulated) Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Wacker Neuson owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Wacker Neuson repair guides →