Wacker Neuson G 25 — Preparing for Automatic/Remote Start-Up (Deep Sea)
Operation · Remote start circuit
For the Wacker Neuson G 25, from the Wacker Neuson owner's manual.
Applies to: Wacker Neuson G 25
Before you start
- Verify remote switch contacts are OPEN before pressing AUTO mode.
Procedure
- Attach a jumper wire between the two remote run terminals.
- Set genset controller power switch to ON.
- Press the AUTO mode button.
- Wait for engine to crank, start, and run.
- Press Stop/Reset to stop the engine.
- Remove the jumper wire.
- Leave power switch ON and close main circuit breaker.
- Press AUTO mode button.
- Secure generator by closing and locking all doors.
Tools required
- Jumper wire (minimum 16-gauge insulated) Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Source: Wacker Neuson owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.