Procedure

  1. Set the multimeter for diode measurement.
  2. Connect the negative test probe to B+ and the positive test probe to each of the three stator windings.
  3. Take readings of the three stator windings.
  4. Switch the test probes and take three more readings.
  5. One time the instrument should read 400–1200 mV (conducting direction); the other time it should read OL.

Tools required

  • Multimeter (diode measurement) Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 400–1200 mV conducting direction; OL reverse

Source: Volvo Penta service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.