Perkins 1106C-70TA / 1106D-70TA — Battery or Battery Cable - Disconnect
Maintenance
For the Perkins 1106C-70TA / 1106D-70TA, from the Perkins owner's manual.
Applies to: Perkins 1106C-70TA, Perkins 1106D-70TA
Parts for this job
Part numbers from the service-parts lists for Perkins 1106C-70TA, Perkins 1106D-70TA. Verify against your serial number before ordering; some links are affiliate links.
Procedure
- Turn start switch to OFF. Turn ignition switch to OFF and remove key and all electrical loads.
- Disconnect negative battery terminal. Ensure cable cannot contact terminal. When four 12 volt batteries are involved, two negative connections must be disconnected.
- Remove positive connection.
- Clean all disconnected connections and battery terminals.
- Use fine grade sandpaper to clean terminals and cable clamps until bright. Do not remove material excessively. Coat with silicone lubricant or petroleum jelly.
- Tape cable connections to help prevent accidental starting.
- Proceed with necessary system repairs.
- To connect battery, connect positive connection before negative connection.
Tools required
- fine grade sandpaper Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Full service-parts list: Perkins 1106C-70TA →, Perkins 1106D-70TA →
Source: Perkins owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.