Home›Repair guides›Northern Lights›Stopping engine

Northern Lights — Stopping engine

Operation

From a Northern Lights operator's manual covering: 753, L753, L843, L854, M354-G, M753, M843, M854, M892. Check it applies to your exact model before use.

Applies to: Northern Lights 753, Northern Lights M753, Northern Lights M843, Northern Lights 854A engine, Northern Lights 854B engine

Before you start

  • Master switch must not be switched off when engine is running.

Procedure

  1. Remove all loads from generator set before shutdown.
  2. Run engine at 1000 RPM no load for two minutes before stopping.
  3. Set throttle at low idle.
  4. Pull stop control or stop cable until engine stops.
  5. Turn off key switch.
  6. If leaving vessel, switch off master switch and close all fuel and cooling water cocks.

Specs & values

  • Run at 1000 RPM no load for two minutes.

Full service-parts list: Northern Lights 753 →, Northern Lights M753 →, Northern Lights M843 →

Source: Northern Lights operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Northern Lights repair guides →