Northern Lights — Stopping engine
Operation
From a Northern Lights operator's manual covering: 753, L753, L843, L854, M354-G, M753, M843, M854, M892. Check it applies to your exact model before use.
Applies to: Northern Lights 753, Northern Lights M753, Northern Lights M843, Northern Lights 854A engine, Northern Lights 854B engine
Before you start
- Master switch must not be switched off when engine is running.
Procedure
- Remove all loads from generator set before shutdown.
- Run engine at 1000 RPM no load for two minutes before stopping.
- Set throttle at low idle.
- Pull stop control or stop cable until engine stops.
- Turn off key switch.
- If leaving vessel, switch off master switch and close all fuel and cooling water cocks.
Specs & values
- Run at 1000 RPM no load for two minutes.
Full service-parts list: Northern Lights 753 →, Northern Lights M753 →, Northern Lights M843 →
Source: Northern Lights operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.