Northern Lights M944T3F — Install siphon break

Installation

For the Northern Lights M944T3F, from the Northern Lights service manual.

Applies to: Northern Lights M944T3F

Before you start

  • Generator sets with wet exhaust near or below water line must use a siphon break to prevent backflow. Backflow can ruin an engine and possibly sink the vessel.

Procedure

  1. Note two plugged penetrations in top left corner of rear panel. These are ports for siphon break lines.
  2. Remove white plastic hole plugs from inside and replace with two rubber grommets (item 14).
  3. Disconnect hose from sea water pump output and heat exchanger inlet.
  4. Replace single hose with two 3/4" ID lines, one from sea water output, other to heat exchanger inlet.
  5. Hoses must allow mounting siphon break minimum 12 inches above vessel's loaded water line.
  6. Pass lines through two holes in rear panel as indicated per diagram.
  7. See 'Exhaust' section of IM 1000 Installation Manual.

Full service-parts list: Northern Lights M944T3F →

Source: Northern Lights service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.