Northern Lights — Flashing the fields
Testing & diagnosis · generator / AVR
From a Northern Lights owner's manual covering: 643/673, M643, M673, NL643, NL673. Check it applies to your exact model before use.
Applies to: Northern Lights M643, Northern Lights M673, Northern Lights NL643, Northern Lights NL673, Northern Lights L643 / L673 engine
Before you start
- The AVR must be disconnected when flashing fields or it could be ruined.
Procedure
- If there is no voltage buildup on startup (zero volts measured), the generator may have no residual magnetic field.
- Disconnect the AVR before flashing fields or it could be ruined.
- Apply 12 volts DC to terminals K (-) and J (+) as indicated.
- Reconnect AVR and check voltage buildup.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- 12 volts DC to K (-) and J (+)
Full service-parts list: Northern Lights M643 →, Northern Lights M673 →, Northern Lights NL643 →, Northern Lights NL673 →
Source: Northern Lights owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.