Before you start
- Unguarded rotating and moving engine components - ensure nobody is in danger zone.
- Engine noise above 85 dB(A) - wear ear protectors.
Procedure
- Change operating mode selector switch to manual mode.
- Switch preheating pump ON.
- If coolant temperature >40 °C (with preheating) or >5 °C (without), press start button.
- Automatic starting sequence is performed; engine runs at rated speed after sequence completes.
- Close the generator circuit breaker (if provided).
- Apply full load only after engine has reached operating temperature (coolant approx. 75 °C).
Specs & values
- Apply full load at coolant approx. 75 °C
Full service-parts list: MTU 12 V 4000 G23 →, MTU 12 V 4000 G43 →, MTU 12 V 4000 G63 →, MTU 12 V 4000 G83 →, MTU 12 V 4000 Gx3 →, MTU 12V4000 G23 →, MTU 16 V 4000 G23 →, MTU 16 V 4000 G63 →