Procedure
- Remove guard cover.
- Check belt for contamination by oil, cracks, wear and overheating; replace if defective.
- Place belt-tension tester onto drive belt midway between the belt pulleys.
- Press button uniformly down until spring disengagement can be heard and felt.
- Take off belt-tension tester without changing position of indication arm.
- Read off measuring value at intersection of indication arm and 'KG' scale.
- Specified belt tension for new drive belt: 450 N -50 N; used drive belt: 350 N -50 N.
- If measured value deviates, readjust belt tension.
- To adjust: loosen securing screws, tension belt with tensioning nut, tighten securing screw (2) to 40 Nm +/- 4 Nm, tighten securing screw (3).
- Install guard cover.
Tools required
- Belt-tension tester Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- New drive belt 450 N -50 N
- Used drive belt 350 N -50 N
- Securing screw (2) 40 Nm +/- 4 Nm
Source: MTU operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.