MQ Power DCA-220SSV / DCA-220SSVU — Manual Starting Procedure

Operation · Genset

For the MQ Power DCA-220SSV / DCA-220SSVU, from the MQ Power operator's manual.

Applies to: MQ Power DCA-220SSV, MQ Power DCA-220SSVU, Volvo Penta TAD520GE engine, Volvo Penta TAD741GE engine

Before you start

  • NEVER start engine with main, GFCI or auxiliary circuit breakers in ON position.

Procedure

  1. Place main, GFCI and aux. circuit breakers in OFF position.
  2. Verify voltage change-over board is configured for desired output voltage.
  3. Connect load to receptacles or output terminal lugs.
  4. Remove terminal lug plastic cover; tighten terminal nuts securely.
  5. Close all engine enclosure doors.
  6. In cold weather, hold pre-heat button at least 50 seconds.
  7. Place engine speed switch in LOW (down) position.
  8. Place MPEC Control Switch in MANUAL to start engine; run 1-2 minutes, then set speed switch HIGH.

Specs & values

  • Oil pressure approximately 44 to 73 psi (303~503 kPa)
  • Coolant temperature 165 to 203 deg F
  • Engine speed approximately 1600 RPM

Full service-parts list: MQ Power DCA-220SSV →, MQ Power DCA-220SSVU →

Source: MQ Power operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.