Magnum MTT25 / MTT25CAN — Manual Starting of the Unit
Operation · Engine / generator
For the Magnum MTT25 / MTT25CAN, from the Magnum operator's manual.
Applies to: Magnum MTT25, Magnum MTT25CAN, Isuzu 4LE1NYGV-01 / 4LE1NYGV-03E engine, Isuzu 4LE1NYGV-03G / 4LE1NYGV-03E engine
Before you start
- CARBON MONOXIDE: USING A GENERATOR INDOORS CAN KILL YOU IN MINUTES.
- Never start the unit under load. The circuit breakers must be in the OFF (O) position when starting in Manual mode.
Procedure
- Move the Control Power switch to the ON (I) position.
- LCD window displays system information and all LEDs flash, then the Ready screen indicates Manual mode.
- Press ENGINE START; the Prestart screen (if equipped) counts down from 20 seconds to 0.
- The Starting screen is displayed; the engine cranks and starts running.
- The Running screen displays; the 45 second V Detect time delay begins counting down.
- If the engine does not start it pauses 15 seconds and makes up to three crank cycles total.
- If it does not start within three cycles, 'SD START FAIL' is shown; wait two minutes and press FAULT RESET, then ENGINE START.
- Check for excessive noise or vibration and any coolant, oil or fuel leaks before applying loads.
- Check AC output voltage and correct it using the fine voltage adjustment screw (rheostat).
- Check the frequency is approximately 60 Hz with no loads.
- Switch the main circuit breaker to ON (I), then add loads by switching the respective circuit breakers to ON (I).
Specs & values
- Engine operating speed 1800 rpm
- No-load frequency approximately 60 Hz
Source: Magnum operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.