| AnInIOM Sd | AnInIOM Sd | Shutdown alarm configurable on the input of IG-IOM/IGS-PTM. | Shutdown | |
| AnInIOM Wrn | AnInIOM Wrn | Warning alarm configurable on the input of IG-IOM/IGS-PTM. | Warning | |
| Battery Flat | Battery Flat (low battery) | If the controller switches off during starting sequence due to bad battery condition, it doesn't try to start again and activates this protection. | Shutdown | |
| Binary Input | Binary Input | Configurable Warning/Shutdown alarms on the inputs of IL-NT. | | |
| ChrgAlternFail | ChrgAlternFail | Failure of the alternator to charge the battery. | Warning | |
| EmergencyStop | EmergencyStop | If the red emergency stop switch is pushed or opened, shutdown is immediately activated. | Shutdown | Pull out the emergency stop switch to reset. |
| Engine Temp Sd | Engine Temp Sd | Water temperature is greater than Sd Water Temp setpoint. | Shutdown | |
| Engine Temp Wrn | Engine Temp Wrn | Water temperature is greater than Wrn Water Temp setpoint. | Warning | |
| Fgen<, > | Fgen<, > | The generator frequency is out of limits given by Gen >f and Gen <f setpoints. | Shutdown | |
| GCB fail | GCB fail | Failure of the generator circuit breaker. | Shutdown | |
| Igen unbl | Igen unbl | The generator current is unbalanced. | Shutdown | |
| Low BackupBatt | Low BackupBatt | RTC backup battery is flat (low). | Warning | |
| Oil Press Sd | Oil Press Sd | Oil pressure is smaller than Sd Oil Press setpoint. | Shutdown | |
| Oil Press Wrn | Oil Press Wrn | Oil pressure is smaller than Wrn Oil Press setpoint. | Warning | |
| Overload | Overload | The load is greater than the value given by Overload setpoint. | Shutdown | |
| Overspeed | Overspeed | The protection comes active if the speed is greater than Overspeed setpoint. | Shutdown | |
| ParamFail | ParamFail | Wrong checksum of parameters. Happens typically after downloading new firmware or changing of the parameter. The controller stays in INIT mode. Check all parameters, write at least one new parameter. | | Check all parameters; write at least one new parameter. |
| PickupFault | PickupFault | Failure of the magnetic pick up sensor for speed measurement. | Shutdown | |
| Sd IOM fail | Sd IOM fail | Shutdown alarm in case of lost connection to IOM/IGS-PTM module. | Shutdown | |
| SprinkIActive | SprinkIActive | The protection is active if the output Sprinkler is closed. | Warning | |
| Start failed | Start failed | Unit did not start. | Shutdown | Press FAULT RESET to clear the controller after the starter has cooled. |
| Stop fail | Stop fail | Unit did not stop. | Shutdown | |
| Underspeed | Underspeed | During starting, when the RPM reaches the Starting RPM setpoint the starter is switched off and speed can drop under Start RPM again; protection evaluation starts 5 seconds after startup. | Shutdown | |
| Vbat | Vbat | Battery voltage is out of limits given by Batt Undervolt setpoints. | Warning | |
| Vgen unbal | Vgen unbal | The generator voltage is unbalanced more than the value of Volt unbal setpoint. | Shutdown | |
| Vgen<, > | Vgen<, > | The generator voltage is out of limits given by Gen <V and Gen >V setpoints. | Shutdown | |
| WrnMaintenance | WrnMaintenance | The period for servicing is set by the WrnMaintenance setpoint; the protection comes active if the running hours of the engine reach this value. | Warning | Reset the Time to Service reminder to the 250 hour interval. |