Home›Repair guides›Kohler›Voltage Regulator Adjustment - CC

Kohler — Voltage Regulator Adjustment - CC

Adjustments

From a Kohler service manual covering: 10C, 10CC, 10CFC, 10CFZ, 12C, 12CFC, 12CFZ, 40CZ, CZ/12-Lead. Check it applies to your exact model before use.

Applies to: Kohler 10C, Kohler 12C, Ford VSG-411 (10 kW) / VSG-413 (12 kW) engine

Before you start

  • Heat sink contains high voltage.

Procedure

  1. With set off, turn remote rheostat to mid-point.
  2. Turn voltage, Volts/Hz, and stability pots fully counterclockwise.
  3. Start set; rotate voltage pot to desired output voltage.
  4. Rotate stability pot clockwise until minimum light flicker.
  5. Install jumper on governor -2.5Hz/Freq terminals.
  6. Rotate Volts/Hz pot clockwise until voltage begins to drop.
  7. Remove jumper from governor circuit board.
  8. Readjust voltage and stability pots if necessary.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Cut-in frequency 57.5 Hz for 60 Hz; 47.5 Hz for 50 Hz
  • Voltage adjustment range 100-130 FridayParts $30.67 V

Full service-parts list: Kohler 12C →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.