Kohler — Voltage Calibration using RDC2 Menus

Adjustments · Normal and Emergency source voltage

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Only authorized personnel should open the enclosure.

Procedure

  1. On the RDC2 controller, navigate to the ATS Status menu; navigate to the Normal Voltage display.
  2. Measure voltage across lugs NL1 and NL2 with a digital voltmeter.
  3. If the controller display does not match the voltmeter, press Select (voltage flashes).
  4. Press Up or Down arrow to change the display to match the voltmeter reading.
  5. Press Select to save the setting.
  6. For 3-phase models, repeat for NL2-NL3 and NL3-NL1.
  7. Start the generator set; navigate to the Emergency Voltage display.
  8. Measure voltage across lugs EL1 and EL2; calibrate as above if needed.
  9. For 3-phase models, repeat for EL2-EL3 and EL3-EL1.
  10. Stop the generator set.