Kohler — Voltage Calibration Using RDC2 Keypad

Adjustments · Controller voltage calibration

From a Kohler service manual covering: 14/20RCA/RCAL, 14RCA, 20RCA, 26RCA, 26RCA/RCAL. Check it applies to your exact model before use.

Applies to: Kohler 14RCA, Kohler 20RCA, Kohler 26RCA, Kohler CH740 / CH1000 / CH1006 engine

Procedure

  1. With set off, connect DVM to measure output voltage L1-L2 (AC volts).
  2. Press RUN to start generator set.
  3. Press Select, navigate to Generator Metering menu.
  4. Press Select to display Volts L1-L2; compare with voltmeter.
  5. If incorrect, press Select (flashes), adjust with arrows, press Select to save.
  6. Wait 30-60 seconds for voltmeter reading to stabilize.
  7. For three-phase, repeat for L2-L3 and L3-L1.
  8. Press OFF to stop generator set.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Fnew = (Vmeter / Vcontrol) x Fold

Full service-parts list: Kohler 14RCA →, Kohler 20RCA →, Kohler 26RCA →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.