Kohler TP-6808 — Wire Insulation Breakdown Test Procedure

Testing & diagnosis · transfer switch wiring

For the Kohler TP-6808, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Only authorized personnel should open the enclosure.

Procedure

  1. Disconnect all power sources and the load from the transfer switch.
  2. Disconnect the transfer switch wiring harness from the controller at P1.
  3. Use a hi-pot tester or meggar to check insulation resistance.
  4. Hi-pot maximum potential 500 VAC; maximum test time 1 second.
  5. Verify measured insulation resistance exceeds 1.24 megohms.
  6. Replace faulty components if insulation breakdown is detected.

Tools required

  • hi-pot tester or meggar Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Minimum insulation resistance 1.24 megohms
  • Hi-pot max 500 VAC for 1 second

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.