Kohler TP-6808 — Voltage to the Coil Test Procedure A

Testing & diagnosis · solenoid coil

For the Kohler TP-6808, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Only authorized personnel should open the enclosure.

Procedure

  1. Disconnect the leads to the Emergency source (lower) coil.
  2. Connect voltmeter across disconnected leads; verify no voltage present.
  3. With switch in normal position, disconnect Normal source; generator starts.
  4. Verify rated voltage is applied as controller attempts to transfer to Emergency.
  5. Unit should attempt to transfer 3 times before fail-to-transfer fault.
  6. Press OFF to stop the generator set and reset the fault condition.
  7. Reconnect leads; manually transfer to Emergency; repeat for Normal coil.

Tools required

  • digital voltmeter or multimeter Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.