Home›Repair guides›Kohler›Position-Indicating Microswitch Test Procedure (3-phase only)

Kohler TP-6808 — Position-Indicating Microswitch Test Procedure (3-phase only)

Testing & diagnosis · position-indicating microswitches

For the Kohler TP-6808, from the Kohler service manual.

Browse Kohler generators & specs →

Procedure

  1. Press OFF; disconnect engine starting battery, negative lead first.
  2. Disconnect utility power to generator set and power to the ATS.
  3. Connect ohmmeter or test lamp across terminals NO and C of switch LSN or SN.
  4. Manually operate the transfer switch; verify NO contact opens and closes.
  5. Repeat for the NC contact; it should open when pressed, close when released.
  6. Verify there is no continuity between the NO and NC terminals.
  7. Repeat steps for switch LSE or SE.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Kohler repair guides →