Kohler TP-6808 — Millivolt Drop Test Procedure

Testing & diagnosis · transfer switch main contacts

For the Kohler TP-6808, from the Kohler service manual.

Browse Kohler generators & specs →

Before you start

  • Only authorized personnel should open the enclosure.

Procedure

  1. Apply a balanced load of at least 10% of switch rating.
  2. Measure voltage on both sources from source lug to load lug.
  3. Take several readings to ensure accuracy.
  4. Use an ammeter to measure current flow through the circuit.
  5. Calculate contact resistance using R = V / I.
  6. Compare calculated resistance to maximum; replace contactor if too high.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • R = V ÷ I
  • 100--200 Amp max contact resistance 0.250 milliohms
  • 300/400 Amp max contact resistance 0.200 milliohms

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.