Kohler — Status Indicator Test Procedure (GM84662-KP2-QS)

Testing & diagnosis · Load shed relays / status indicator

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Operate the generator set in RUN mode, not AUTO; the ATS must NOT transfer for this test.

Procedure

  1. Press RUN on the RDC2 or DC2 generator set controller to start the generator set.
  2. Press the TEST button on the indicator panel to exercise the first relay.
  3. Press TEST again for the next relay, repeating to cycle through all relays in order.
  4. The test mode ends automatically after 15 minutes; to end manually hold TEST for 5 seconds or press OFF or AUTO.

Specs & values

  • Test mode ends automatically after 15 minutes