Kohler — Source Voltage and Frequency Check Procedure

Testing & diagnosis · Transfer switch sources (Normal and Emergency)

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Only authorized personnel should open the enclosure.
  • Do not connect or disconnect the controller harness when the power is connected.

Procedure

  1. Press OFF on the generator set controller and verify the generator set is off.
  2. Disconnect both power sources from the transfer switch.
  3. Disconnect the contactor wiring harness from P13 (single-phase) or P1 (3-phase) on the interface board.
  4. Manually operate the transfer switch to position E.
  5. Close the utility source circuit breaker; check utility voltage across NL1-NL2 and each to neutral.
  6. For three-phase, repeat voltage checks across NL1-NL3 and NL3-NL1.
  7. Disconnect Source N; manually operate to position N; press RUN to start the generator set.
  8. Check generator voltage and frequency at EL1 and EL2 and each to neutral.
  9. For three-phase, repeat checks across EL2-EL3 and EL3-EL1.
  10. If voltage/frequency do not match the nameplate, adjust the generator set.
  11. Stop the generator set; disconnect both sources; reconnect the harness to P13 or P1.
  12. Close and lock the enclosure door; reconnect both power sources; press AUTO.

Tools required

  • Digital voltmeter (DVM) with insulated probes Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.