Kohler — Siphon Break Inspection

Maintenance

From a Kohler operator's manual covering: 11EKOD, 11EKOZD, 5EFKOD, 5EFKOZD, 6EKOD, 6EKOZD, 7- 9EFKOZD, 7EFKOZD, 9- 11EKOZD, 9EFKOD, 9EFKOZD, 9EKOZD. Check it applies to your exact model before use.

Applies to: Kohler 11EKOZD, Kohler 5EFKOD, Kohler 6EKOD, Kohler 7EFKOZD, Kohler 9EFKOZD, Kohler 9EKOZD

Before you start

  • Ensure that the siphon break's cap is tight before operating the generator set.

Procedure

  1. Stop the generator set.
  2. Remove the retaining cap and remove the reed valve for inspection.
  3. Use a mild detergent to remove residue and oxidation from the reed valve.
  4. Clear blockage from the reed valve opening.
  5. Replace the siphon break if the reed valve is cracked or the material has hardened or deteriorated.
  6. Install the reed valve into the mounting base with the valve downward.
  7. Install and only finger tighten the retaining cap.