Before you start

  • Power still present on input side of utility circuit breaker

Procedure

  1. Prevent emergency generator from starting
  2. Press OFF button on generator controller
  3. Disconnect power to battery charger
  4. Remove battery cables (negative lead first)
  5. Remove outer enclosure door
  6. Move utility source circuit breaker to OFF
  7. Replace door and attach padlock
  8. Do not remove protective barrier around utility connections

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.