Kohler RDT-CFNC-0200ASE — SPD Module Replacement
Repair & overhaul · Surge Protective Device (SE model)
For the Kohler RDT-CFNC-0200ASE, from the Kohler service manual.
Applies to: Kohler RDT
Before you start
- Hazardous voltage. Will cause severe injury or death. Must be installed and serviced by qualified electrical personnel.
- Deenergize all power sources before servicing.
Procedure
- Remove the ATS enclosure front panel and move the battery charger circuit breaker to OFF.
- Turn the generator set OFF and disconnect power to the battery charger.
- Disconnect the generator set starting battery, negative lead first.
- Move the Normal service disconnect circuit breaker to OFF.
- Remove the ATS enclosure inner panel.
- Disconnect the SPD leads from the normal source breaker, ground, neutral, and terminal block.
- Remove the 4 SPD mounting screws.
- Install the new module and tighten mounting screws to 3 Nm (26 in-lb).
- Connect the SPD leads per the service entrance wiring diagram.
- Replace the enclosure inner panel.
- Close the Normal and Emergency service disconnect circuit breakers.
- Reconnect the generator set starting battery, negative lead last.
- Reconnect power to the battery charger and close its breaker.
- Replace the ATS enclosure front panel.
- Put the generator set into AUTO mode.
Tools required
- screwdriver Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- SPD mounting screw torque 3 Nm (26 in-lb)
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.