Home›Repair guides›Kohler›Output Voltage and Frequency Adjustment

Kohler — Output Voltage and Frequency Adjustment

Adjustments · ADC 2100 Controller

From a Kohler service manual covering: 10E, 10EG, 10EOR, 10EORD, 10EORZ, 10EORZD, 10EOZ, 10ERG, 10REOD, 10REOZD, 11.5EFOZD, 11EFG…. Check it applies to your exact model before use.

Applies to: Kohler 10EORZ, Kohler 10EOZ, Kohler 10ERG, Kohler 10REOZD, Kohler 11.5EFOZD

Before you start

  • The generator set must be running during these adjustments.
  • The engine speed (frequency) adjustment menus are not accessible on models with mechanical governors.

Procedure

  1. Move the master switch to RUN; the engine starts and runtime hours display.
  2. Hold the Select button about 5 seconds until the program version number displays.
  3. Press the down arrow key then the up arrow key 3 times to enter adjustment mode.
  4. 1P: adjust voltage coarse in large increments (approximately 5-7 volts per step).
  5. 2P: adjust voltage fine in smaller increments (approximately 0.5-0.7 volts per step).
  6. Adjust voltage stability (gain) coarse and fine.
  7. 3P: set volts/Hz (00=low, 09=high).
  8. 4P: adjust engine governor speed coarse and fine.
  9. 5P: adjust engine governor stability (gain) coarse and fine.
  10. Enter SAVE mode and save settings before exiting the adjustment mode.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Kohler 10EORZ →, Kohler 10EOZ →, Kohler 10ERG →, Kohler 10REOZD →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.