Kohler — Optional Load Bank Testing
Maintenance · Generator Set
From a Kohler service manual covering: 1000ROZD71, 100RZ82, 1200ROZD71, 125GGKB/4957867, 1500R0ZD, 200REOZV, 200TH2608, 20ROZJ81, 230RE0ZD, 250ROZ281, 275DSE, 275REOZV…. Check it applies to your exact model before use.
Applies to: Kohler 200REOZV, Detroit Diesel 12V149TI engine, Cummins/Onan NTA855 CS2 engine, Cummins/Onan KTA3067 engine, Caterpillar D 343 engine, Caterpillar 3512 D1 engine, Cummins/Onan NT855C engine
Procedure
- Perform 4-hour resistive load bank test at 80% of generator nameplate capacity.
- Record all performance data at fifteen minute intervals including oil pressure, water temperature, voltage and frequency.
- Identify proper operation of fuel system, cooling system and overall condition of engine/generator set.
- Load bank testing shall be performed with no interruption to the normal power supply.
Full service-parts list: Kohler 200REOZV →, Detroit Diesel 12V149TI engine →
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.