Kohler — Optional Load Bank Testing

Maintenance · Generator Set

From a Kohler service manual covering: 1000ROZD71, 100RZ82, 1200ROZD71, 125GGKB/4957867, 1500R0ZD, 200REOZV, 200TH2608, 20ROZJ81, 230RE0ZD, 250ROZ281, 275DSE, 275REOZV…. Check it applies to your exact model before use.

Applies to: Kohler 200REOZV, Detroit Diesel 12V149TI engine, Cummins/Onan NTA855 CS2 engine, Cummins/Onan KTA3067 engine, Caterpillar D 343 engine, Caterpillar 3512 D1 engine, Cummins/Onan NT855C engine

Procedure

  1. Perform 4-hour resistive load bank test at 80% of generator nameplate capacity.
  2. Record all performance data at fifteen minute intervals including oil pressure, water temperature, voltage and frequency.
  3. Identify proper operation of fuel system, cooling system and overall condition of engine/generator set.
  4. Load bank testing shall be performed with no interruption to the normal power supply.

Full service-parts list: Kohler 200REOZV →, Detroit Diesel 12V149TI engine →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.