Kohler — Operation Sequence Test

Testing & diagnosis · Automatic transfer switch operation

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Before you start

  • Hazardous voltage. Only authorized personnel should open the enclosure.

Procedure

  1. Press the OFF button on the generator set controller.
  2. Disconnect ALL power sources to the transfer switch.
  3. Manually operate the transfer switch to the normal position (do not manually operate with power connected).
  4. Close and secure the enclosure door and apply the normal power source; verify Utility Available LED.
  5. Press the AUTO button on the generator set controller.
  6. Disconnect the normal power source and wait for the engine start time delay (replace controller if engine not signalled within +/-10% of setting).
  7. Reconnect the emergency source and check Generator Power Available LED; wait for normal-to-emergency transfer time delay.
  8. Reconnect the normal power source and wait for the emergency-to-normal retransfer time delay.
  9. Wait for the engine cooldown time delay (replace controller if engine not signalled to stop within +/-10% of setting).

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Replace controller assembly if engine start, transfer, retransfer, or cooldown is not within +/-10% of the setting

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.