Home›Repair guides›Kohler›Motor Replacement (Alternate Design 100-200 Amp Single-Phase)

Kohler — Motor Replacement (Alternate Design 100-200 Amp Single-Phase)

Repair & overhaul · Contactor motor

From a Kohler service manual — check it applies to your exact model before use.

Browse Kohler generators & specs →

Procedure

  1. Disconnect the control wiring, 8 quick connects, from the motor to be replaced.
  2. Before pulling the motor out, make sure the transfer switch is in the Normal position.
  3. Slide the pole cover out from its location.
  4. Remove the 2 screws holding the motor.
  5. Firmly pull the motor away from the power poles.
  6. Use a 5/8 in. wrench on the side of the poles to apply a small clockwise torque toward the normal contacts while sliding the motor back into position.
  7. Replace the pole cover by sliding it back until it clicks.
  8. Install the two screws and torque to 8-10 in. lb. (0.9-1.1 Nm).
  9. Operate the switch to the standby position and back to normal to check engagement.
  10. Reconnect the wire harness, matching the marking tags with the motor labels (8 quick connects).

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Motor mounting screws torque 8-10 in. lb. (0.9-1.1 Nm)

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Kohler repair guides →