Kohler — Governor System Operation Test Procedure
Testing & diagnosis · Governor system / magnetic pickup
From a Kohler service manual covering: 12RES, 8.5/12 RES, 8.5RES. Check it applies to your exact model before use.
Applies to: Kohler 12RES, Kohler 8.5RES, Kohler CH20 engine, Kohler CH 740 engine
Before you start
- Hazardous voltage. Operate the generator set only when all guards and electrical enclosures are in place.
Procedure
- Verify carburetor throttle linkage is connected to the stepper motor.
- Look for broken or loose wiring or plug connections if stepper motor moves erratically.
- Check stepper motor operation at startup; note throttle positions.
- If throttle moves fully open then steps to and stays fully closed, check the magnetic pickup.
- Connect a voltmeter to the magnetic pickup leads; check for 1.75 volts AC minimum during cranking.
- If below 1.75 VAC, verify magnetic pickup air gap is 0.5 mm (0.020 in.); adjust as needed.
- After adjusting gap, recheck voltage; replace magnetic pickup if still below 1.75 VAC.
- Disconnect magnetic pickup leads and open circuit breaker to test controller governing function.
- Move throttle shaft/stepper motor fully counterclockwise (closed throttle).
- Start the generator set; stepper motor should step clockwise to wide open throttle and remain there.
- Place master switch in STOP; check stepper motor connections (leads 1A, 1B, 2A, 2B to P1-4, P1-5, P1-6, P1-7).
- Check stepper motor coil resistance across pins 2 and 3 and across pins 1 and 4.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- Magnetic pickup air gap 0.5 mm (0.020 in.)
- Magnetic pickup output 1.75 VAC minimum during cranking
- Stepper motor coil resistance 38.5 ohms per half coil
Full service-parts list: Kohler 12RES →, Kohler 8.5RES →
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.