Kohler — Frequency Adjustment Procedure

Adjustments · Governor system

From a Kohler service manual covering: 12RES, 8.5/12 RES, 8.5RES. Check it applies to your exact model before use.

Applies to: Kohler 12RES, Kohler 8.5RES, Kohler CH20 engine, Kohler CH 740 engine

Before you start

  • Hazardous voltage. Operate the generator set only when all guards and electrical enclosures are in place.

Procedure

  1. Open the generator set line circuit breaker.
  2. Attach a frequency meter to the AC output leads.
  3. Start and run the generator set until normal operating temperature (at least 10 minutes).
  4. Use the ADC controller to adjust the electronic governor speed (parameter 4P) for 60 Hz (or 50 Hz).
  5. Check stability with no load; decrease gain (parameter 5P) until stable if speed hunts or surges.
  6. Repeat steps 4 and 5 to obtain rated frequency and stable operation.
  7. Save the settings.
  8. Apply rated load and observe frequency; no load and full load frequencies should be within 0.4 Hz of rated.
  9. Check for hunting and surging at full load; increase gain until engine hunts, then decrease in small steps.
  10. Remove the load and observe frequency; repeat step 4 if frequency changed.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 60 Hz units operate at 3600 rpm; 50 Hz units run at 3000 rpm
  • No load and full load frequencies within 0.4 Hz of rated

Full service-parts list: Kohler 12RES →, Kohler 8.5RES →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.