Home›Repair guides›Kohler›Exerciser Setup (Standard Exerciser)

Kohler — Exerciser Setup (Standard Exerciser)

Operation · controller

From a Kohler service manual — check it applies to your exact model before use.

Applies to: Kohler RDT

Before you start

  • Hazardous voltage. Only authorized personnel should open the enclosure.

Procedure

  1. Press and hold Exercise button approximately 3 seconds until GEN Available LED flashes for unloaded exercise.
  2. Press and hold Exercise button at least 6 seconds until GEN Available and GEN Position LEDs flash for loaded exercise.
  3. Exercise runs weekly for 20 minutes at the set day and time.
  4. Press and hold Exercise button 2 seconds to end the exercise early.
  5. Press and hold both Exercise and Test buttons at least 6 seconds to reset the exerciser.

Specs & values

  • Duration: 20 minutes
  • Frequency: weekly
  • Type: loaded 3-5 seconds, unloaded 6+ seconds

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.