Kohler — Engine Start Contact Test Procedure

Testing & diagnosis · controller engine start contacts

From a Kohler service manual — check it applies to your exact model before use.

Applies to: Kohler RDT

Before you start

  • Hazardous voltage. Only authorized personnel should open the enclosure.

Procedure

  1. Press OFF on the generator set controller.
  2. Disconnect the generator set engine starting battery, negative lead first.
  3. Disconnect power to the transfer switch by opening the normal and emergency source circuit breakers.
  4. Open the enclosure and disconnect P2 from the ATS controller board.
  5. Connect an ohmmeter or test lamp across engine start terminals 3 and 4 on P2; verify contacts are closed.
  6. If contacts 3 and 4 are not closed, replace the controller circuit board.
  7. Reconnect the normal source and monitor contacts; verify contacts open after engine cooldown time delay.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.