Kohler — Controller Resetting (Following System Shutdown or Warning)
Operation · Decision-Maker 3500 controller
From a Kohler operator's manual covering: 125REZGT, 30--125REZGT, 30REZG, 30REZGT, 50REZG, 70REZGT. Check it applies to your exact model before use.
Applies to: Kohler 125REZGT, Kohler 30REZG, Kohler 30REZGT, Kohler 50REZG, Kohler 70REZGT
Before you start
- Read the Safety Precautions and Instructions section before proceeding.
Procedure
- Disconnect the generator set load using the line circuit breaker or automatic transfer switch.
- Correct the cause of the fault shutdown or warning.
- Start the generator set by pressing OFF/RESET then RUN.
- Test operate the generator set to verify correction of the shutdown cause.
- Press OFF/RESET to stop the generator set.
- Press the generator set AUTO button.
- Silence the controller alarm horn by pressing the ALARM SILENCE button.
- Reconnect the generator set load via the line circuit breaker or automatic transfer switch.
Full service-parts list: Kohler 125REZGT →, Kohler 30REZG →, Kohler 30REZGT →, Kohler 50REZG →, Kohler 70REZGT →
Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.