Kohler — Controller Configuration
Adjustments · ADC 2100 Controller
From a Kohler service manual covering: 10E, 10EG, 10EOR, 10EORD, 10EORZ, 10EORZD, 10EOZ, 10ERG, 10REOD, 10REOZD, 11.5EFOZD, 11EFG…. Check it applies to your exact model before use.
Applies to: Kohler 10EORZ, Kohler 10EOZ, Kohler 10ERG, Kohler 10REOZD, Kohler 11.5EFOZD
Before you start
- Be sure to save the new settings immediately before exiting the configuration mode; changes are lost if the controller times out (about 1 minute).
Procedure
- Hold the Select button and move the master switch to RUN to enter configuration mode.
- Press the down arrow key then the up arrow key 3 times to enter configuration mode (password).
- Set the voltage/frequency parameter Uu for the model.
- Set the unit configuration parameter Uc (marine, standby, mobile).
- Set the engine type parameter Ec.
- Press the up arrow at the Adnc display to enter advanced configuration mode.
- Set the engine data input type Ed.
- Set the battery voltage Bt (12 or 24 VDC).
- Set the communications parameter Cn.
- Enter save mode and save your settings before exiting.
Full service-parts list: Kohler 10EORZ →, Kohler 10EOZ →, Kohler 10ERG →, Kohler 10REOZD →
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.