Kohler 30RCL / 38RCLC — Installation Guidelines

Installation · Genset placement

For the Kohler 30RCL / 38RCLC, from the Kohler service manual.

Applies to: Kohler 30RCL, Kohler 38RCLC

Before you start

  • Minimum 8 feet clearance from exhaust end
  • Verify state and local codes for installation distance requirements

Procedure

  1. Position exhaust aimed away from or parallel to structure
  2. Do not direct exhaust at play areas or gathering spaces
  3. Maintain minimum 5 feet distance from windows, vents, doors or openings
  4. Install minimum 18 inches from structure per NFPA 37
  5. Close windows and doors on adjacent walls
  6. Keep furnace and intakes at least 10 feet from exhaust end
  7. Provide 4 inch thick concrete pad extending 6 inches beyond genset
  8. Maintain clear area with no combustibles within 8 feet of exhaust
  9. Keep sensitive plants and patio furniture at least 8 feet from exhaust

Full service-parts list: Kohler 30RCL →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.