Kohler 24RCL — Generator Installation
Installation · Genset placement
For the Kohler 24RCL, from the Kohler service manual.
Applies to: Kohler 24RCL
Before you start
- Minimum clearances required per NFPA 37
- Local codes may require greater distances
Procedure
- Exhaust must be aimed away from or parallel to the structure.
- Do not direct exhaust at play areas, patios, or congregation areas.
- Place nearest window, vent, door at least 5 feet from exhaust end.
- Install minimum 18 inches from structure per NFPA 37 (verify local codes).
- Keep windows and doors on adjacent walls closed.
- Place furnace and similar intakes at least 10 feet from exhaust.
- Install 4-inch thick concrete pad extending 6 inches beyond genset.
- Remove plants, shrubs, combustibles from minimum 8-foot clearance area.
- Position sensitive plants and furniture at least 8 feet from exhaust.
Full service-parts list: Kohler 24RCL →
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.