Home›Repair guides›Kohler›Generator Installation

Kohler 24RCL — Generator Installation

Installation · Genset placement

For the Kohler 24RCL, from the Kohler service manual.

Applies to: Kohler 24RCL

Before you start

  • Minimum clearances required per NFPA 37
  • Local codes may require greater distances

Procedure

  1. Exhaust must be aimed away from or parallel to the structure.
  2. Do not direct exhaust at play areas, patios, or congregation areas.
  3. Place nearest window, vent, door at least 5 feet from exhaust end.
  4. Install minimum 18 inches from structure per NFPA 37 (verify local codes).
  5. Keep windows and doors on adjacent walls closed.
  6. Place furnace and similar intakes at least 10 feet from exhaust.
  7. Install 4-inch thick concrete pad extending 6 inches beyond genset.
  8. Remove plants, shrubs, combustibles from minimum 8-foot clearance area.
  9. Position sensitive plants and furniture at least 8 feet from exhaust.

Full service-parts list: Kohler 24RCL →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.