Kohler 14RES / 20RES — Voltage Adjustment, RDC Controller

Adjustments · Generator output

For the Kohler 14RES / 20RES, from the Kohler service manual.

Applies to: Kohler 14RES, Kohler 20RES

Before you start

  • Hazardous voltage.
  • Moving parts.

Procedure

  1. With generator off, connect digital multimeter to output leads or load-side outlet; set to AC voltage.
  2. Start generator with RUN button.
  3. Adjust parameter 1P until output voltage reaches desired value.
  4. Adjust voltage stability (gain, parameter 2P) to minimize light flicker.
  5. Readjust voltage if necessary.
  6. Save settings.
  7. Stop generator.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Coarse/fine voltage change per step: 85--180 VAC 5/0.5 VAC; 180--360 VAC 7/0.7 VAC.

Full service-parts list: Kohler 14RES →, Kohler 20RES →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.