Kohler 14RES / 20RES — Field-Connection Terminal Block Wiring
Installation
For the Kohler 14RES / 20RES, from the Kohler service manual.
Applies to: Kohler 14RES, Kohler 20RES
Before you start
- Hazardous voltage.
- Backfeed to utility.
Procedure
- Drill holes for conduit fittings; feed cables through openings.
- Connect transfer switch emergency source leads to L1 and L2 on terminal block.
- Connect neutral (L0) and ground (GRD) from ATS and main panel.
- For RRT transfer switch, connect interface panel to ATS1--ATS4 before connecting engine starting battery.
- For RDT/RSB transfer switch or remote start/stop, connect engine start leads to terminals 3 and 4.
- Connect utility power to terminals labelled Utility; source must be GFCI protected.
Specs & values
- Route low-voltage communication leads through separate conduit.
Full service-parts list: Kohler 14RES →, Kohler 20RES →
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.