Home›Repair guides›Kohler›Resetting the Controller after a Fault Shutdown

Kohler 12RES / 8.5RES — Resetting the Controller after a Fault Shutdown

Operation · Advanced Digital Control (ADC 2100)

For the Kohler 12RES / 8.5RES, from the Kohler operator's manual.

Applies to: Kohler 12RES, Kohler 8.5RES, Kohler CH20 engine, Kohler CH 740 engine

Before you start

  • Always identify and correct the cause of a fault shutdown before resetting the controller.

Procedure

  1. Move the generator set master switch to OFF/RESET.
  2. Disconnect the generator set from the load using the line circuit breaker or ATS.
  3. Identify and correct the cause of the fault shutdown.
  4. Start the generator set by moving the master switch to RUN and test operate it.
  5. Move the generator set master switch to OFF/RESET.
  6. Reconnect the generator set to the load using the line circuit breaker or ATS.
  7. Move the master switch to AUTO for startup by remote transfer switch or remote start/stop switch.

Full service-parts list: Kohler 12RES →, Kohler 8.5RES →

Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.