Home›Repair guides›Kohler›Fuel Conversion Procedure (natural gas to LP vapor)

Kohler 12RES / 8.5RES — Fuel Conversion Procedure (natural gas to LP vapor)

Adjustments · Multi-fuel block

For the Kohler 12RES / 8.5RES, from the Kohler operator's manual.

Applies to: Kohler 12RES, Kohler 8.5RES, Kohler CH20 engine, Kohler CH 740 engine

Before you start

  • Do not adjust the factory-sealed fuel-metering adjustments on the fuel block.
  • Explosive fuel vapors can cause severe injury or death.
  • Accidental starting can cause severe injury or death.

Procedure

  1. Place the master switch in OFF, disconnect battery charger power, disconnect battery (negative lead first), and turn off fuel supply.
  2. Remove the hose clamp and fuel hose from the hose fitting in the fuel block.
  3. Remove the hose fitting from the natural gas outlet port in the fuel block.
  4. Remove the plug from the LP port, clean it, apply fresh pipe sealant, and install it into the natural gas outlet port.
  5. Clean the hose fitting, apply fresh pipe sealant to the threads, and install it into the LP port.
  6. Slide the hose onto the fitting and secure it with the clamp.
  7. For 12RES only: connect the DSAM leads together for natural gas (disconnect for LP vapor).
  8. Connect and turn on the new fuel supply; recheck the master switch is OFF.
  9. Reconnect the battery (negative lead last) and reconnect battery charger power.
  10. Start the generator set by moving the master switch to RUN and check for leaks with a gas leak detector.
  11. Move the generator set master switch to the AUTO position.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Kohler 12RES →, Kohler 8.5RES →

Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Kohler repair guides →