Home›Repair guides›Kohler›Disconnect the Continuous Power Mode Jumper

Kohler 12RES / 8.5RES — Disconnect the Continuous Power Mode Jumper

Installation · ADC 2100 controller, connector P7

For the Kohler 12RES / 8.5RES, from the Kohler operator's manual.

Applies to: Kohler 12RES, Kohler 8.5RES, Kohler CH20 engine, Kohler CH 740 engine

Before you start

  • Accidental starting can cause severe injury or death.

Procedure

  1. Prevent starting: move master switch to OFF/RESET, disconnect battery charger power, disconnect battery (negative lead first).
  2. Remove the controller: disconnect harness connector P1 (35-pin), and the J15 and J16 connectors.
  3. Remove the controller back cover: note and disconnect the three pink master switch leads, remove cover screws and back cover.
  4. Locate connector P7 near the top; remove the jumper from pins 1 and 2 (connect across pins 2 and 3 for storage if three pins).
  5. Replace the back cover and secure the cover screws.
  6. Reconnect the three pink connectors to the master switch.
  7. Reconnect the J15 and J16 connectors.
  8. Reconnect the battery (negative lead last) and reconnect battery charger power.
  9. Place the generator set master switch in the AUTO position.

Full service-parts list: Kohler 12RES →, Kohler 8.5RES →

Source: Kohler operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.