Home›Repair guides›Kohler›Voltage Regulator Adjustment

Kohler 10CC / 10CCOZ-Mobile — Voltage Regulator Adjustment

Adjustments · PowerBoost V voltage regulator

For the Kohler 10CC / 10CCOZ-Mobile, from the Kohler service manual.

Applies to: Kubota V1305BG-2 engine

Before you start

  • Hazardous voltage can cause severe injury or death. The heat sink of the voltage regulator contains high voltage.

Procedure

  1. Turn Voltage, Volts/Hz, and Stability pots fully counterclockwise; connect voltmeter to AC circuit or outlet.
  2. Start generator set. Rotate Voltage Adjustment pot clockwise or counterclockwise until desired output voltage is achieved.
  3. Rotate Stability pot clockwise until minimum light flicker is obtained.
  4. Readjust Voltage Adjustment pot if necessary.
  5. Adjust engine speed to desired cut-in frequency (57.5-58 Hz for 60 Hz models).
  6. Rotate Volts/Hz Adjustment pot clockwise until voltage level begins to drop.
  7. Readjust engine speed to normal (63 Hz/1890 rpm for 60 Hz models).
  8. Readjust Voltage Adjustment pot and Stability pot if necessary.
  9. Stop generator set.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Voltage Adjustment pot range 190-270 Volts (line-to-line)
  • Volts/Hz factory setting 57.5 Hz on 60 Hz models
  • Normal 63 Hz/1890 rpm for 60 Hz models

Full service-parts list: Kubota V1305BG-2 engine →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.