Kohler 10CC / 10CCOZ-Mobile — Cooling System Flushing and Filling

Maintenance

For the Kohler 10CC / 10CCOZ-Mobile, from the Kohler service manual.

Applies to: Kubota V1305BG-2 engine

Before you start

  • Hot coolant and steam. Before removing pressure cap stop generator, allow to cool and loosen pressure cap to relieve pressure.

Procedure

  1. Open petcocks at the radiator and engine block and let the system completely drain.
  2. Remove the pressure cap to make draining easier.
  3. Drain, clean, and flush coolant recovery tank, if used.
  4. Flush system with clean water before filling with recommended coolant.
  5. Close both drains and fill the radiator to the proper level with recommended coolant mixture.
  6. Replace the radiator cap and operate the engine until the thermostat opens and the upper hose becomes hot.
  7. Stop the engine, allow to cool, and add coolant to raise level just below the overflow tube.

Specs & values

  • Coolant capacity (10CCOZ-Mobile inline radiator): 5.1 qts. (4.8 L)
  • 50% ethylene glycol and 50% clean, softened water

Full service-parts list: Kubota V1305BG-2 engine →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.