Generac — Testing Under Load

Testing & diagnosis · Generator AC output

From a Generac service manual covering: NP-50G, NP-50LP, NP-66G/LP, Q-40G, Q-55G/LP, Q-70G/LP. Check it applies to your exact model before use.

Applies to: Generac NP-50G, Generac NP-50LP, Generac Q-40G, Generac NP-50G/LP engine

Procedure

  1. Apply electrical loads equal to about 75-100% of unit's rated wattage/amperage capacity.
  2. Check frequency with electrical load applied; frequency should not drop below about 58 Hz under load.
  3. Let unit run at least 30 minutes with load applied; check unit is not running excessively hot and adequate cooling air flow is available.
  4. Do not allow unit to overheat during prolonged operation.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 58 Hz minimum under load

Full service-parts list: Generac NP-50G →, Generac NP-50LP →, Generac Q-40G →

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.